Product Overview

Document No. 129-217
Installation Instructions
September 30, 2002
Page 4 of 6 Siemens Building Technologies, Inc.
EA0746R1
EARTH GROUND
ISOLATING CLASS 2
TRANSFORMER FOR
24 Vac POWER
120 Vac
1
0
Y2
Y1
G
NEUT
CONTROLLER
24
Vac
NEUT
CONTROLLER
24
Vac
3Y1 Y2
4
G
11
Cm1
5
c1
3
4
5
c2
1000
100%
0%
100%
0%
cba
EA0448R2
ASZ7.3ASC9.3DU
Figure 12. Non-Spring Return SKD82.50U.
Connecting Terminals
G System Potential 24 Vac (+)
Y1 Outward movement of coupling piece (0 to 1)
Y2 Inward movement of coupling piece (1 to 0)
Cm1 Limit switch for 100% stroke
c1 ASC9.3DU double auxiliary switch
c2 ASC9.3DU double auxiliary switch
1000
ASZ7.3 potentiometer
The diagram shows all possible connections. How
many and which are used depend on the application.
EA0745R1
EARTH GROUND
ISOLATING CLASS 2
TRANSFORMER FOR
24 Vac POWER
120 Vac
21
Y2
Y1
G
1
0
0
NEUT
CONTROLLER
24
Vac
ASZ7.3ASC9.3DU
3Y1 Y2
4
G
11
Cm1N.O.
5
c1
3
4
5
c2
1000
100%
0%
100%
0%
cba
21
EA0447R2
Figure 13. Spring Return SKD82.51U.
Connecting Terminals
G System Potential 24 Vac (+)
21 System Neutral (SN)
Y1 Outward movement of coupling piece (0 to 1)
Y2 Inward movement of coupling piece (1 to 0)
Cm1 Limit switch for 100% stroke
c1 ASC9.3DU double auxiliary switch
c2 ASC9.3DU double auxiliary switch
1000
ASZ7.3 potentiometer
The diagram shows all possible connections. How
many and which are used depend on the application.
Start-Up
Check the wiring for proper connections.
Consult Technical Instructions 155-180P25 for detailed
commissioning information.
Normally Closed Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve opens.
Inward (1 to 0): Valve closes.
Normally Open Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve closes.
Inward (1 to 0): Valve opens.
Three-Way Valve
Actuator pressure cylinder moves:
Outward: Valve opens between port NC and C.
Inward: Valve opens between ports NO and C.
NOTE: The valve body assembly determines the
complete assembly action.