Installation Instructions

Document No. 129-217
Installation Instructions
September 24, 2018
Page 4 of 6 Siemens Industry, Inc.
Wiring for SKD82…U, Continued
Figure 12. Non-Spring Return SKD82.50U.
Connecting Terminals
G
System Potential 24 Vac (+)
Y1
Outward movement of coupling piece (0 to 1)
Y2
Inward movement of coupling piece (1 to 0)
Cm1
Limit switch for 100% stroke
c1
ASC9.3DU double auxiliary switch
c2
ASC9.3DU double auxiliary switch
1000
ASZ7.3 potentiometer
The diagram shows all possible connections. How
many and which are used depend on the application.
Figure 13. Spring Return SKD82.51U.
Connecting Terminals
G
System Potential 24 Vac (+)
21
System Neutral (SN)
Y1
Outward movement of coupling piece (0 to 1)
Y2
Inward movement of coupling piece (1 to 0)
Cm1
Limit switch for 100% stroke
c1
ASC9.3DU double auxiliary switch
c2
ASC9.3DU double auxiliary switch
1000
ASZ7.3 potentiometer
The diagram shows all possible connections. How
many and which are used depend on the application.
Start-Up
Check the wiring for proper connections.
Consult Flowrite 599 Series SKD6xU Electronic Valve
Actuators 24 Vac Proportional Technical Instructions
155-180P25 for detailed commissioning information.
Normally Closed Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve opens.
Inward (1 to 0): Valve closes.
Normally Open Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve closes.
Inward (1 to 0): Valve opens.