Data Sheet for Product

19
Siemens CM1N4561en
Smart Infrastructure 2021-06-21
Technical data
Power supply
Operating voltage
SKD32.. AC 230 V ± 15 %
SKD82..
AC 24 V ± 20 % (SELV/PELV)SKD6..
SKD62/MO
Frequency 50 / 60 Hz
Maximum power consumption at 50 Hz
SKD32.21 16 VA / 12 W
SKD32.50 11 VA / 8 W
SKD32.51 17 VA / 12 W
SKD82.50, SKD82.50U 9 VA / 7 W
SKD82.51, SKD82.51U 14 VA / 10 W
SKD60.. 10 VA / 8 W
SKD62.. 14 VA / 10 W
External supply cable fuse
SKD32.. Min. 0.5 A, slow
Max. 6 A slow
SKD82.. Min. 1 A, slow
Max. 10 A slow
SKD6..
Function data
Positioning time at 50 Hz
1)
SKD32.21 Opening 30 s
Closing 10 s
SKD32.5..
SKD82.5..
Opening, closing 120 s
SK6.. Opening 30 s
Closing 15 s
Spring-return time
1)
SKD32..
8 s
SKD82..
SKD62.. 15 s
Positioning force 1000 N
Nominal stroke 20 mm
Maximum permissible medium temperature (valve fitted) -25...150 °C
< 0 °C:
Requires stem heater ASZ6.6
Signal inputs / signal outputs
Control signal
SKD32..
3-position
SKD82..
SKD6.. DC 0…10 V
DC 4…20 mA
0…1000 Ω