Product Overview
9/18
Siem ens Electrohydraulic actuators for valves CM1N4561en
Building Technologies 2014-06-18
ASC1.6
auxiliary switch
switching point 0…5 % stroke
See section «Technical data» on page 11 for more information.
Engineering notes
Conduct the electrical connections in accordance with local regulations on electrical
installations as well as the internal or connection diagrams.
Safety regulations and restrictions designed to ensure the safety of people and
property must be observed at all times!
For media below 0 °C the ASZ6.5 or ASZ6.6 stem
heater is required to keep the valve from freezing. For
safety reasons the stem heater is designed for an
operating voltage of AC 24 V / 30 W.
For this case, do not insulate the actuator bracket and
the valve stem, as air circulation must be ensured. Do
not touch the hot parts without prior protective
measures to avoid burns.
Non-observance of the above may result in accidents
and fires!
Recommendation: Above 140 °C insulating the
valves is strictly recommended.
4567
Z
1
1
Observe admissible temperatures, refer to «Use» on page 1 and «Technical data» on
page 11.
If an auxiliary switch is required, its switching point should be indicated on the plant
schematic.
Every actuator must be driven by a dedicated controller (refer to
«Connection diagrams», page 14).
Mounting instructions
Mounting Instruction 74 319 0325 0 for fitting the actuator to the valve are by packed in
the actuator packaging. The instructions for accessories are enclosed with the
accessories themselves.
Accessories Installation instructions Accessory Mounting instructions
ASC1.6 G4563.3 4 319 5544 0 ASZ6.5 M4563.7 4 319 5564 0
ASC9.3 G4561.3 4 319 5545 0 ASK50 M4561.5 4 319 5549 0
SKD... 74 319 0326 0 ASZ7.3… 74 319 0247 0
SKD… M3250 74 319 0325 0
ASZ6.6 M4501.1 74 319 0750 0
90°
90°
SKD62.., SKD60..
Caution
Caution
Orientation