Data Sheet for Product

19
Siemens CM1N4566en
Smart Infrastructure 2021-06-07
Technical data
Power supply
Operating voltage
SKC32.. AC 230 V ± 15 %
SKC82..
AC 24 V ± 20 % (SELV/PELV)SKC6..
SKC62/MO
Frequency 50 / 60 Hz
Maximum power consumption at 50 Hz
SKC32.60, SKC32.60/F 18 VA / 14 W
SKC32.61, SKC32.61/F 24 VA / 18 W
SKC82.60, SKC82.60U 15 VA / 12 W
SKC82.61, SKC82.61U 19 VA / 14 W
SKC60.. 17 VA / 13 W
SKC62.. 21 VA / 15 W
External supply cable fuse
SKC32.. Min. 0.5 A, slow
Max. 6 A slow
SKC82.. Min. 1.6 A, slow
Max. 10 A slow
SKC6..
Function data
Positioning time at 50 Hz
1)
SKC32.6.. Opening, closing
120 s
SKC82.6.. Opening, closing
120 s
SK6.. Opening 120 s
Closing 20 s
Spring-return time
1)
SKC32.61, SKC32.61/F
18 s
SKC82.61, SKC82.61U
SKC62.. 20 s
Positioning force 2800 N
Nominal stroke 40 mm
Maximum permissible medium temperature (valve fitted) -25...220 °C
< 0 °C:
Requires stem heater ASZ6.6
Signal inputs / signal outputs
Control signal
SKC32..
3- position
SKC82..
SKC6.. DC 0…10 V
DC 4…20 mA
0…1000 Ω