Data Sheet for Product
18
Siemens CM1N4566en
Smart Infrastructure 2021-06-07
WARNING
R
isk of injury
● Disconnect electrical connections from the terminals as neede.
● The actuator must be properly installed prior to recommissioning the valve.
Recommendation
SKC6..:
Trigger stroke calibration after maintenance.
Repair:
See Spare parts [➙ 12]
WARNING
Verl
Risk of injury through broken housing or cover
Dismounting the actuator with broken housing from the valve can release the highly
tensioned spring return, which can cause flying parts and injury.
● NEVER dismount actuator from valve.
● Dismount valve-actuator combination (control device) as complete unit.
● Disassembly only by qualified personnel.
● Send the control device along with an error report to the local Siemens office for
analysis and disposal.
● Mount new control device (valve and actuator) properly.
Disposal
WARNING
Tensioned spring return
Opening the actuator housing can release the highly tensioned return spring, which can
cause flying parts and injuries.
● Do not open the actuator housing.
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.
Warranty
Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations". Siemens rejects any and all warranties in the event that
third-party products are used.