Data Sheet for Product
17
Siemens CM1N4566en
Smart Infrastructure 2021-06-07
Operation
Automatic operation
For automatic operation, the crank [2] on the manual adjustment knob [1] must be engaged.
If not engaged, turn the crank counter-clockwise until the display window [3] shows neither
the scale [4] nor the crank engagement bar.
Manual operation
For manual operation, swing out the crank [2] so that the display window [3] becomes visible.
By rotating the crank or the manual adjustment knob [1], the display window shows the
engagement bar and/or the scale dial [4] with stroke indication.
Engaged crank [2] on the manual adjustment knob [1] Display window with invisible scale dial and crank
engagement bar
Swung-out crank; display window [3] Display window with scale dial [4] and stroke indication
in mm
Maintenance
The actuators are maintenance-free.
When servicing the control device:
WARNING
Risk of burns from hot actuator brackets
The actuator brackets on heating plants can also become hot from the contact with the hot
valve during operation. The temperature of the actuator bracket can reach 100 °C.
When servicing the actuator:
● Switch off both pump and operating voltage.
● Close the main shutoff valve in the piping.
● Release pressure in the pipes and allow them to cool off completely.