Product Overview

13/16
Siemens Building Technologies Electro-hydraulic actuators for valves CM1N4564E
HVAC Products 13.02.2009
Internal diagrams
SKB32.51
AC 230 V, 3-Position
4564G0 1
Y1 Y2 3 3 a b c
100 %
0 %
100 %
0 %
N 4 545
Cm1
c1 c2
ASC9.3 ASZ7.3..
21
n
11
SKB32.50
AC 230 V, 3-Position
4564G0 2
Y1 Y2 3 3 a b c
100 %
0 %
100 %
0 %
N4545
Cm1
c1 c2
ASC9.3 ASZ7.3..
Cm1 end switch
n solenoid valve for spring-
return
c1, c2 ASC9.3 double auxiliary
switch
a, b, c ASZ7.. potentiometer
Y1 Positioning signal «open»
Y2 Positioning signal «close»
21 spring-return function
N neutral conductor
SKB82.51
AC 24 V, 3-Position
45 64G03
Y1 Y2 3 3 a b c
100 %
0 %
100 %
0 %
G4545
Cm1
c1 c2
ASC9.3 ASZ7.3..
21
n
11
SKB82.50
AC 24 V, 3-Position
4564G04
Y1 Y2 3 3 abc
100 %
0 %
100 %
0 %
G 4 545
Cm1
c1 c2
ASC9.3 ASZ7.3..
Cm1 end switch
n solenoid valve for spring-
return
c1, c2 ASC9.3 double auxiliary
switch
a, b, c ASZ7.. potentiometer
Y1 Positioning signal «open»
Y2 Positioning signal «close»
21 spring-return function
G System potential
SKB60, SKB62
SKB60U, SKB62U
SKB62UA
AC 24 V, DC 0...10 V,
4...20 mA, 0...1000
U
Z
Y
M
G0
G
Speisung
Einstellungen und Anzeige
MMI
Eingang
Zwangsteuerung
(Signalpriorität)
Eingang
Valve Seat
Detection
Valve Jam
Detection
DC 0 ...10 V
oder
4 ... 20 mA
DC 0 ...10 V
oder
4 ... 20 mA
– G
– G0
– 0 ...1000
Ω
Hub
voll offen
0 ...100 %
ganz geschlossen
0 ...100 %
Hub
Pumpe
Solenoid
Hub
Ventil
01706de
Ausgang
U position indication
Z override control
Y positioning signal
M measuring neutral
G0 operating voltage AC 24 V:
system neutral (SN)
G operating voltage AC 24 V:
system potential (SP)
Connection terminals
U
Z
G0
G
Y
M
operating voltage AC 24 V: system neutral (SN)
operating voltage AC 24 V: system potential (SP)
Positioning signal DC 0...10 (30) V or DC 4...20 mA
Measuring neutral (= G0)
Position indication DC 0...10 V or DC 4...20 mA
Override control (functionality see page 7)
c1
3
45
01804
SKB6..
Auxiliary switch
ASC1.6