Install Instructions

Document Number: 129-185
Installation Instructions
September 30, 2002
Page 5 of 8
SKB/C62U
Calib.
Status
DIPSwitches
FunctionsSeeBelow
LEDStatus
Indication
StrokeCalibration
Connection
Terminals
EA1068R1
G0
AC24V
50/60Hz 0...10V
4...20mA
G
G0
Chm
GYMUZ
OK
Green
Status
Calib.
Red
Calib.
Error
Valve
Jam
1 2
Figure 23. SKB/C62U.
DIP
Switches
1
Selection of
Control Signal
2
Selection of Flow
Characteristic
ON 4 to 20 mA Modified*
OFF
(Factory Setting)
0 to 10 Vdc Default
*Changing the default setting will modify an equal
percentage valve to a linear flow characteristic. When
set to default, the flow characteristic is determined by
the valve body.
GB1M
G0
Y1
GM
Z
G0
Y
U
BM
G(SP)
F1
Y1
N1
B1
G0(SN)
32
1
M
Sensor
TemperatureLimiter
Controller
Actuator
B1
F1
N1
Y1
AC24V
EA1074R1
Figure 24.
Connecting Terminals
24 Vac
G System Potential (SP)
G0 System Neutral (SN)
Y Control Input 0 to 10 Vdc or 4 to 20 mA
(DIP switch selectable)
Z Override Input
(See Technical Instructions 155-163P25)
M Measuring Neutral
U Position Indicator for 0 to 10 Vdc or
4 to 20 mA .
Wiring for SKB/C82...U
Non-Spring Return
SKB82.50U, SKC82.60U
EA0746R1
EARTH GROUND
ISOLATING CLASS 2
TRANSFORMER FOR
24 Vac POWER
120 Vac
1
0
Y2
Y1
G
NEUT
CONTROLLER
24
Vac
NEUT
CONTROLLER
24
Vac
3Y1 Y2
4
G
11
Cm1
5
c1
3
4
5
c2
1000
100%
0%
100%
0%
cba
EA0217R3
ASZ7.3ASC9.3BCU
Figure 25. Non-Spring Return.
Connecting Terminals
G System Potential 24 Vac (+)
Y1 Downward movement of coupling piece (0 to 1)
Y2 Upward movement of coupling piece (1 to 0)
Cm1 Limit switch for 100% stroke
c1 ASC9.3BCU double auxiliary switch
c2 ASC9.3BCU double auxiliary switch
1000
ASZ7.3 potentiometer
The diagram shows all possible connections. How
many and which are used depend on the application.
Spring Return SKB82.51U and SKC82.61U
GY1Y221
11
EA0226R2
Figure 26.