Install Instructions
Document Number: 129-185
Installation Instructions
September 30, 2002
Page 4 of 8
4
EA0147R1
3
Figure 18.
0
1
24 mm
5
EA0148R1
Figure 19.
6
EA0149R1
SKB 8 x 360°
OR
SKC 16 x 360°
Figure 20.
7
EA0150R1
Figure 21.
Wiring
CAUTION: Use care when removing the
knockout. Do not damage the circuit board.
If possible, use the top knockout position.
Do not use autotransformers. Use earth ground
isolating step-down Class 2 transformers.
Determine supply transformer rating by summing total
VA of all actuators used. The maximum rating for a
Class 2 step-down transformer is 100 VA.
Actuator
Power
Consumption
Actuators Per
Class 2 Supply
Circuit
*
(80% of
transformer VA)
SKB62U 17 VA 4
SKC62U 28 VA 2
SKB82.50U 10 VA 8
SKB82.51U 15 VA 5
SKC82.60U 19 VA 4
SKC82.61U 20 VA 4
* Operating more actuators requires
additional transformers or separate 100 VA
power supplies.
0
1
N V1 V2 21 11
N V1 V2 21 11
2
1
3
4
EA0152R1
Figure 22.
• Wiring for SKB/C62U is shown in Figures 22
and 23.
• Wiring for SKB/C82…U is shown in Figures 24
through 26.
• The position output signal U will switch from 0
to 10 Vdc to 4 to 20 mA when a 4 to 20 mA
input signal is selected and used on the
terminal.