Data Sheet for Product
Technical Instructions Flowrite 599 Series SKB/C Electronic Valve Actuator
Document Number 155-171P25 3-Position (Floating) Control
September 25, 2018
Page 6 Siemens Industry, Inc.
Start-Up
Check the wiring for proper connections.
The valve body assembly determines the complete assembly action.
Normally Closed Valve
Actuator pressure cylinder moves outward (0 to 1): Valve opens.
Actuator pressure cylinder moves inward (1 to 0): Valve closes.
Normally Open Valve
Actuator pressure cylinder moves outward (0 to 1): Valve closes.
Actuator pressure cylinder moves inward (1 to 0): Valve opens.
Three-way Valve
Actuator pressure cylinder moves outward (0 to 1): Valve opens between port NC
and C.
Actuator pressure cylinder moves inward (1 to 0): Valve opens between ports NO
and C.
Manual Operation
Figure 9. The Manual Setting Knob in Manual Position.
Release the crank arm of the manual setting knob located on the top of the actuator. As
you turn the crank, a red scale appears in a window in the manual setting knob. This
scale indicates the effective valve stroke in millimeters. Each complete revolution (360°)
is equal to 2 mm of stroke. The numbers 2 to 20 or 2 to 40 are visible depending on the
stroke of the actuator.
If a signal is sent to the actuator while it is in manual operation, the actuator will move
but the control will not be accurate. The valve cannot be commanded to its 0% position
while in manual operation.