User Guide
Flowrite EA 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
July 11, 2011
Siemens Industry, Inc. Page 9
Start-up, Continued
Advanced Features
Calib.
Status
EA1077R1
LED Status
Indication
Stroke Calibration
Rotary Switches
LO and UP
Connection
Terminals
G0
AC 24V
50/60Hz 0 ... 10V
4 ... 20mA
G
G0
Chm
GYMUZ
OK
Green
Status
Calib.
Red
Calib.
Error
Valve
Jam
1 2 3 4
Figure 13. DIP Switches.
1
2
3
4
DIP Switches
(From Left to Right)
Select
Direction of
Operation
Sequence Control
or
Stroke Limit Control
Selection of
Control
Signal
Selection of
Flow
Characteristic
ON Reverse-acting Sequence control 4 to 20 mA Modified*
OFF
(Factory Settings)
Direct-acting Stroke limit control 0 to 10 Vdc Default
*Changing the default setting will modify an equal percentage valve to a linear flow characteristic. When
set to default, the flow characteristic is determined by the valve body.