Stroke Calibration
To determine the stroke positions 0% and 100% in the valve, calibration is required when the
valve/actuator are commissioned for the first time. The actuator must be mechanically
connected to a valve and must have a supply voltage of 24 Vac. The calibration procedure can
be repeated as often as necessary
CAUTION:
Before starting calibration, be sure that the manual adjuster is set to Automatic for
the actual values to register.
There is a slot on the printed circuit boards for the actuators. To
initiate the calibration procedure, the contacts inside this slot must
be short-circuited (possibly with a screwdriver). See
EA1065R1
Figure 11.
Figure 11.
Automatic calibration proceeds as follows (see Figure 12):
Actuator runs to the 0% stroke position (1), the green LED
flashes.
Actuator then runs to the 100% stroke position (2), the
green LED flashes.
0 %
1
2
3
y
100 %
Stroke
EA1066R1
Measured values are stored in the EPROM.
The actuator now moves to the position defined by control
signal Y or Z (3), and the green LED now glows steady
(normal operation).
Figure 12.
Automatic Calibration.
Throughout this procedure, output U is inactive, meaning
the values only represent actual positions when the green
LED stops flashing and remains on continuously.
Table 2. LED Status.
LED Display Function Action
ON Normal Operation Automatic operation
Green
Stroke calibration In
Progress
Wait for calibration to be
completed (LED stops flashing)
Flashing
Faulty stroke calibration - Check mounting
- Restart stroke calibration (by
short-circuiting calibration slot)
ON
Internal Error - Replace electronics
Flashing Valve plug jammed Check the valve
Red
- Check mains
No power supply
OFF
- Replace electronics
Faulty electronics