User Guide

Technical Instructions Flowrite EA 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
July 11, 2011
Page 4 Siemens Industry, Inc.
Direction of Operation
Direct acting / reverse acting 0 to 10 Vdc; 10 to 0 Vdc
4 20 mA; 20 to 4 mA
0 to 1000 ohm/1000 to 0 ohm
Advanced Features
Stroke Limit Control
Range of lower limit 0% to 45% adjustable
Range of upper limit 100% to 55% adjustable
Sequence Control
Starting Point of Sequence (Start) 0 to 15V adjustable
Operating Range of Sequence (Span) 3 to 15V adjustable
Accessories
ASC1.6 Auxiliary switch
Sends a signal to indicate that the valve is
in the 0% stroke position.
The switching point is fixed at the 0%
stroke position.
Switching capacity 24 Vac
4A resistive,
2A inductive
Figure 1. Auxiliary Switch.
Lowest recommended current 10 mA
599-00417 Packing heating element for SKD
599-00418 Packing heating element for SKB/C
EA0393R1
This heater allows the stem to move freely in
valves that control fluids at temperatures below
32°F (0°C). It reduces ice crystal formation on
the stem which may damage the packing.
Operating Voltage 24 Vac
Figure 2. Packing Heating Element.
Heating Output 20 W
599-10065 The SKB/C actuator is UL listed to
meet NEMA Type 3R requirements (a degree
of protection against rain, sleet, and damage
from external ice formation) when installed with
this weather shield and outdoor-rated conduit
fittings in the vertical position. See Service Kits
for replacement ultraviolet resistant cable ties.
EA0729R1
Figure 3. SKB/C Weather Shield.
599-10071 The SKD actuator is UL listed to
meet NEMA TYPE 3R requirements (a degree
of protection against rain, sleet, and damage
from external ice formation) when installed with
this weather shield and outdoor-rated conduit
fittings in the vertical position. See Service Kits
for replacement ultraviolet resistant cable ties.
EA0853R1
Figure 4. SKD Weather Shield.