Data Sheet for Product
8
Siemens CM1N4564en
Smart Infrastructure 2021-06-07
Override control Z
SKB60, SKB62..
The override control input Z can be operated in the following modes of operation:
Z-mode
No function Fully open Closed Override with 0…1000 Ω Signal addition
SKB62UA only
Connections
Transfer
Equal percentage or
linear
Equal percentage or linear
●  Z-contact not
connected
●  Z-contact directly
connected to G
●  Z-contact directly
connected to G0
●  Z-contact connected to
M via resistor R
●  Starting position at 50 Ω
End position at 900 Ω
●  Z-contact
connected to R of
frost protection
monitor QAF21..
or QAF61..
●  Valve stroke follows
Y-input
●  Y-input has no effect ●  Valve stroke
follows Y and
R(Z) signal
Sh
own
operation modes are based on the factory setting
“direct acting”
.
Y-input has no effect in Z-mode.
Selection of direction of operation
SKB60 (from version ..L), SKB62UA
●  With normally-closed valves, “direct acting” means that with a signal input of 0 V, the
valve closes (applies to all Siemens valves listed under Equipment combinations [➙ 12]).
●  With normally-open valves, “direct acting” means that with a signal input of 0 V, the valve
is open.
Direct acting Reverse acting Stroke
Input DC 0...10 V
DC 4...20 mA
0...1000 Ω
Input DC 0...10 V
DC 4...20 mA
0...1000 Ω
The mechanical spring
-
return function is not affected by the direc
tion of operation selected.