Data Sheet for Product

8
Siemens A6V12057657_en--_a
Smart Infrastructure 2021-03-05
Parameter
513 Backup mode
(replacement mode)
RW 0 = Go to backup position / 1 = Not available / 2 =
Deactivated
2 = Deactivated
514 Backup position RW 0...100 % = 0...10000 0 %
515 Backup timeout RW 0...65535 900 [s]
516 Start-up setpoint RW 0...100 % = 0...10000 0 %
764 Modbus address RW 1...248 / 255 = "Unassigned" 255 =
"Unassigned"
765 Baud rate RW 0 = Auto / 1 = 9600 / 2 = 19200 / 3 = 38400 / 4 =
57600 / 5 = 76800 / 6 = 115200
0
766 Transmission format RW 0 = 1-8-E-1 / 1 = 1-8-O-1 / 2 = 1-8-N-1 / 3 = 1-8-N-2 0
767 Bus termination RW 0 = Off / 1 = On
120 Ω electronically switchable
0
768 Bus conf. command RW 0 = Ready / 1 = Load / 2 = Discard 0
769 Status R See Register 769 "Status" [ 10] -
Reg. Name R/W Value Example
Device information
1281 Factory Index R 2 Bytes
Each coding an ASCII character
5A 00 Z 00
Device is of series “Z”
1282 Factory Date
HWord
R 2 Bytes
The lower coding the year (hex)
Reg. 1282 000F
Reg. 1283 0418
HWord LWord
1283 Factory Date
LWord
R 2 Bytes
HByte coding the month (hex)
LByte coding the day (hex)
-- YY MM DD
Hex 00 0F 04 18
Dec 00 15 04 24
Date of manufacture = April 24,
2015
1284 Factory sequence no.
HWord
R
Hword + LWord = hex representation
of sequence number:
Reg. 1284 000A
Reg. 1285 A206
AA206(hex) 696838 (dec)
Device has sequence number
696838
1285 Factory sequence no.
LWord
R
1409 ASN [Character
16...15]
R
Each register 2 Bytes
Each coding an ASCII character
ASN is coded beginning with reg.
1409
0x53 4B = SK
0x42 36 = B6
0x32 2F = 2/
0x4D 4F = MO
ASN is SKB62/MO
1410 ASN [Char. 14...13] R
1411 ASN [Char. 12...11] R
1412 ASN [Char. 10...9] R
1413 ASN [Char. 8...7] R
1414 ASN [Char. 6...5] R
1415 ASN [Char. 4...3] R
Reserve
1416 ASN [Char. 2...1] R
Supported function codes
Function codes
03 (0x03) Read holding registers
04 (0x04) Read input registers
06 (0x06) Write single register
16 (0x10) Write multiple registers (limit: max. 120 registers within one write operation)