Data Sheet for Product
5
Siemens A6V12057657_en--_a
Smart Infrastructure 2021-03-05
LED colors and blinking patterns
Color Blinking pattern Description
Green 1 s on / 5 s off Normal mode without bus traffic
Flickering Normal mode with bus traffic
Orange / green 1 s orange / 1 s green Device is in override control mode
Orange 1 s on / 1 s off Bus parameter not yet configured
1 s on / 5 s off Device is in backup mode (replacement
mode)
Red Permanently lit Mechanical error, device blocked, manual
intervention or calibration
1 s on / 5 s off Internal error
0.1 s on / 1 s off Invalid configuration, e.g. Min = Max
Blue Flickers 1 x after indicating the address Bus termination active
Reset actuator with pushbutton
1. Press button > 10 s
LED blinks orange
2. Release the button while LED is still blinking
LED blinks another 3 s
3. Release the button whithin these 3 s
Reset is cancelled
4. Press button after these 3 s
LED is red (Reset) while the device restarts.
Enter address using pushbutton
Display current address (starting from lowest address position)
The Modbus address can be set without an extra tool using pushbutton addressing.
To display the current Modbus address, press the button <1s.
Colors
1-digit: red 10-digit: green 100-digit: orange
Example for address 124:
LED
Note The address is entered and displayed beginning at the lowest digit (1st digit), see figure
above.
(Example: 124 starts with 4 x red)