Data Sheet for Product

4
Siemens A6V12057657_en--_a
Smart Infrastructure 2021-03-05
User interface
Pushbutton operation
Action Pushbutton operation Feedback message
Current Modbus address
(starting from lowest address
position)
Button press <1 s 1st digit (single digit): red
10-digit (double digit): green
100-digit (triple digit): orange
The LED blinks 1 x blue after the
address indication if bus termination
is switched on
Example:
124 = 4 x red, 2 x green, 1 x orange
Switch on/off bus termination
Switch-on Press the button 3 times Blinking or flashing of LED stops
(termination mode).
Briefly press the button 1 x Blue LED flashes 1 x.
Press button until the LED turns red RED LED is lit (confirmation).
Release button LED not lit.
Address is indicated.
LED blinks 1 x blue after the address
indication
Device enters normal mode.
Switch off Press the button 3 times Blinking or flashing of LED stops
(termination mode).
Briefly press the button 1 x RED LED is lit (confirmation).
Release button Device enters normal mode.
Enter Modbus address using
pushbutton
Button press >1 s and <5 s See Enter address using pushbutton
[ Error! Bookmark not defined.]
Enable pushbutton addressing
(together with Climatix
TM
controllers)
Button press >5 s and <10 s Red LED is lit and goes off after 5 s.
Release button Orange LED lit.
Reset to factory settings Button press >10 s LED flashes orange.