Page 78 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01
mmmmm
Appendix C
HART Conformance and Command Class
SITRANS LC 500 transmitter Conformance and Command Class summary.
Command
Number
Description Usage
Conformance Class #1
0 Return Unique Identifier Universal
1 Read Primary Variable
Conformance Class #1A
0 Return Unique Identifier Universal
2 Read PV Current and Percent of Range
Conformance Class #2
11 Read Unique Identifier Associated with Tag Universal
12 Read Message
13 Read Tag, Descriptor, and Date
14 Read Primary Variable Sensor Information
15 Read Primary Variable Output Information
16 Read Final Assembly Number
Conformance Class #3
3 Read Dynamic Variables and PV Current Universal
33 Read Selected Dynamic Variables Common Practice
48 Read Additional Transmitter Status Common Practice
50 Read Dynamic Variable Assignments Common Practice
Conformance Class #4
34 Write PV Damping Value Common Practice
35 Write Primary Variable Range Values
36 Set Primary Variable Upper Range Value
37 Set Primary Variable Lower Range Value
38 Reset Configuration Changed Flag
40 Enter/Exit Fixed Primary Var. Current Mode
Conformance Class #5
6 Write Polling Address Universal
17 Write Message
18 Write Tag, Descriptor and Date
19 Write Final Assembly Number
44 Write Primary Variable Units Common Practice
45 Trim Primary Variable Current DAC Zero
46 Trim Primary Variable Current DAC Gain
49 Write Primary Variable Sensor Serial Number
59 Write Number of Response Preambles