7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 95
mmmmm
Appendix E
USL is set to 83.50 pF Menu 0C reads 83.50
LSL is set to 7.3 pF Menu 0B reads 7. 3 0
When the process level reaches 90%, the probe is considered covered and the output will
be 20 mA. If the level exceeds USL, the output will be 22 mA. When the process level
drops to 8%, the probe is considered uncovered, and the output will switch to 4 mA. If the
level drops below LSL, the fault signal will be 22 mA.