Pressure transmitter SITRANS P, DS III Series with HART Operating Instructions· 09/2012 SITRANS Answers for industry.
Introduction 1 Safety instructions 2 Description 3 Installing/mounting 4 Connecting 5 Operation 6 Operating functions through HART 7 Functional safety 8 Commissioning 9 SITRANS Pressure transmitter SITRANS P, DS III series with HART Operating Instructions 7MF4.33..
Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Table of contents 1 2 3 4 Introduction...................................................................................................................................................9 1.1 Purpose of this documentation......................................................................................................9 1.2 Product information.......................................................................................................................9 1.3 History........................
Table of contents 5 6 4 4.1.2.1 Incorrect mounting.......................................................................................................................38 4.2 Disassembly................................................................................................................................39 4.3 4.3.1 4.3.2 4.3.3 Installation (except level).............................................................................................................
Table of contents 6.5.5.4 6.5.5.5 6.5.6 6.5.7 6.5.8 6.5.9 6.5.10 6.5.11 6.5.12 6.5.13 7 Blind adjusting of the start of scale value....................................................................................86 Blind adjustment of the full scale value.......................................................................................86 Trimming the zero point...............................................................................................................87 Current transmitter......
Table of contents 8 9 6 7.19 Static configuration data............................................................................................................126 7.20 Flow rate measurement (only differential pressure)..................................................................127 7.21 7.21.1 7.21.2 7.21.3 7.21.4 7.21.5 Diagnostic functions..................................................................................................................128 Overview..........................
Table of contents 9.4.4 10 11 12 13 A Commissioning with vapor.........................................................................................................157 Service and maintenance.........................................................................................................................159 10.1 Basic safety instructions............................................................................................................159 10.2 10.2.1 10.2.2 10.2.3 10.2.
Table of contents B A.2 Literature and standards............................................................................................................215 A.3 Literature and catalogs..............................................................................................................215 A.4 Overview of HART operating structure......................................................................................217 A.5 Technical support...................................................
1 Introduction 1.1 Purpose of this documentation These instructions contain all information required to commission and use the device. It is your responsibility to read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation.
Introduction 1.5 Checking the consignment Edition Remark 09/2012 The following chapters have been changed: ● "General safety notices" chapter ● "Mounting" chapter ● "Functional safety" chapter ● "Technical data" chapter 1.4 Scope of the instructions Table 1-1 1.5 "7MF4.
Introduction 1.7 Notes on warranty 1.6 Transportation and storage To guarantee sufficient protection during transport and storage, observe the following: ● Keep the original packaging for subsequent transportation. ● Devices/replacement parts should be returned in their original packaging. ● If the original packaging is no longer available, ensure that all shipments are properly packaged to provide sufficient protection during transport.
Safety instructions 2.1 2 Precondition for use This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the device. Always keep the information and symbols in a completely legible state. Symbol Explanation Consult operating instructions 2.1.
Safety instructions 2.2 Use in hazardous areas Electromagnetic Compatibility EMC 2004/108/EC Atmosphère explosible ATEX 94/9/EC Pressure Equipment Directive PED 97/23/EC Directive of the European Parliament and of the Council on the approximation of the laws of the Member States relating to electromagnetic compatibility and repealing Directive 89/336/ EEC.
Safety instructions 2.2 Use in hazardous areas ● They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures, aggressive and hazardous media. ● They are authorized, trained, or instructed in carrying out work on electrical circuits for hazardous systems. ● They are trained or instructed in maintenance and use of appropriate safety equipment according to the pertinent safety regulations.
Safety instructions 2.2 Use in hazardous areas WARNING Use of incorrect device parts in potentially explosive environments Devices and their associated device parts are either approved for different types of protection or they do not have explosion protection. There is a danger of explosion if device parts (such as covers) are used for devices with explosion protection that are not expressly suited for this type of protection.
3 Description 3.1 System configuration Overview The pressure transmitter can be used in a number of system configurations: ● as a stand-alone version, supplied with the necessary auxiliary power ● as part of a complex system environment, e.g. SIMATIC S7 System communication Communication is via the HART protocol, using: ● HART Communicator (load 230 ... 1100 Ω) ● PC with HART modem, on which appropriate software is installed, e.g. SIMATIC PDM (load 230 ...
Description 3.2 Application range 3.2 Application range Overview Depending on the version, a transmitter measures corrosive, non-corrosive and hazardous gases, vapors and liquids. You can use the transmitter for the following types of measurement: ● Gauge pressure ● Absolute pressure ● Differential pressure With appropriate parameter settings and the necessary add-on parts (e.g.
Description 3.3 Structure Level This version with mounting flange measures the level of non-corrosive, corrosive and hazardous liquids in open and closed containers. The smallest measuring span is 25 mbar (0.363 psi), the largest 5 bar (72.5 psi). The nominal diameter of the mounting flange is DN 80 or DN 100 or 3" or 4". The negative connection of the measuring cell is kept open when measuring the level of open containers. This measurement is referred to as "measurement against atmosphere".
Description 3.
Description 3.4 Nameplate layout 3.4 Nameplate layout Nameplate with general information The nameplate bearing the Order No. and other important information, such as design details and technical data, is on the side of the enclosure. D-761 81 K arlsr uhe SITRANS P 0 032 PED:SEP Tr ansmit ter fo r pressur e 7MF4033-1EB1 0-1D A1 Fab. Nr. N1LN1 1-0 047 11 V H :DC1 0.5-45 V (not intr.s ave ) outp.:4-20 mA F illing Silik onöl Mat.: Connec. Diaphr. 1.4404 2.
Description 3.5 Measuring point label layout Nameplate with approval information On the opposite side is the nameplate with approval information. This nameplate shows e.g. the hardware and firmware versions. Certificate information is also listed if the transmitter is an ex-version. D-761 81 K arlsr uhe SITRANS II 1/2 G P E x d IIC T4/T6 V H :DC 10. 5 - 4 5 V outp.
Description 3.6 Functional principle 3.6 Functional principle 3.6.1 Overview of mode of operation This chapter describes how the transmitter works. First the electronics are described, and then the physical principle of the sensors which are used with the various device versions for the individual measurement types. 3.6.
Description 3.6 Functional principle Function ● The input pressure is converted into an electrical signal by the sensor ①. ● This signal is amplified by the measuring amplifier ② and digitized in an analog-to-digital converter ③. ● The digital signal is analyzed in a microcontroller ④ and corrected with regard to linearity and thermal characteristics. ● The digital signal is then converted in a digital-to-analog converter ⑤ into the output current of 4 to 20 mA.
Description 3.6 Functional principle ● Flange connection in accordance with EN 61518 ● Flush-mounted process connections 3.6.3.
Description 3.6 Functional principle 3.6.3.
Description 3.6 Functional principle 3.6.3.
Description 3.6 Functional principle 3.6.3.
Description 3.6 Functional principle ● The change in the resistance causes a bridge output voltage proportional to the absolute pressure. 3.6.3.
Description 3.6 Functional principle The inlet pressure (pe) is transferred to the gauge pressure sensor ⑥ via the seal diaphragm ④ and the filling liquid ⑤, displacing its measuring diaphragm. The displacement changes the resistance of the four piezoresistors (bridge circuit) of the gauge pressure sensor. The change in the resistance causes a bridge output voltage proportional to the inlet pressure.
Description 3.8 SIMATIC PDM 3.7 Remote seal Product description ● A remote seal measuring system comprises the following elements: – Remote seal – Transmission line, e.g. capillary line – Measuring device Note Malfunction of the remote seal measuring system If you separate the components of the remote seal measuring system, this results in malfunctioning of the system. Do not separate the components under any circumstances.
Installing/mounting 4.1 4 Basic safety instructions WARNING Wetted parts unsuitable for the process media Danger of injury or damage to device. Hot, toxic and corrosive media could be released if the process medium is unsuitable for the wetted parts. ● Ensure that the material of the device parts wetted by the process medium is suitable for the medium. Refer to the information in "Technical data" (Page 169). WARNING Incorrect material for the diaphragm in Zone 0 Danger of explosion in the hazardous area.
Installing/mounting 4.1 Basic safety instructions Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials. WARNING Exceeded maximum permissible operating pressure Danger of injury or poisoning. The maximum permissible operating pressure depends on the device version.
Installing/mounting 4.1 Basic safety instructions WARNING Incorrect conduit system Danger of explosion in hazardous areas as result of open cable inlet or incorrect conduit system. ● In the case of a conduit system, mount a spark barrier at a defined distance from the device input. Observe national regulations and the requirements stated in the relevant approvals. See also Technical data (Page 169) WARNING Incorrect mounting at Zone 0 Danger of explosion in hazardous areas.
Installing/mounting 4.1 Basic safety instructions WARNING Loss of explosion protection Danger of explosion in hazardous areas if the device is open or not properly closed. ● Close the device as described in Chapter "Connecting the device (Page 60)". WARNING Use of incorrect device parts in potentially explosive environments Devices and their associated device parts are either approved for different types of protection or they do not have explosion protection.
Installing/mounting 4.1 Basic safety instructions 4.1.1 Installation location requirements WARNING Insufficient air supply The device may overheat if there is an insufficient supply of air. ● Install the device so that there is sufficient air supply in the room. ● Observe the maximum permissible ambient temperature. Refer to the information in the section "Technical data (Page 169)". CAUTION Aggressive atmospheres Damage to device through penetration of aggressive vapors.
Installing/mounting 4.1 Basic safety instructions 4.1.2 Proper mounting 4.1.2.1 Incorrect mounting NOTICE Incorrect mounting The device can be damaged, destroyed, or its functionality impaired through improper mounting. ● Before installing ensure there is no visible damage to the device. ● Make sure that process connectors are clean, and suitable gaskets and glands are used. ● Mount the device using suitable tools.
Installing/mounting 4.3 Installation (except level) 4.2 Disassembly WARNING Incorrect disassembly The following dangers may result through incorrect disassembly: - Injury through electric shock - Danger through emerging media when connected to the process - Danger of explosion in hazardous area In order to disassemble correctly, observe the following: ● Before starting work, make sure that you have switched off all physical variables such as pressure, temperature, electricity etc.
Installing/mounting 4.3 Installation (except level) ● Easily accessible ● As close as possible to the measuring point ● Vibration-free ● Within the permitted ambient temperature values Installation configuration The transmitter may in principle be configured above or below the pressure tapping point. The recommended configuration depends on the aggregate state of the medium. Installation configuration for gases Install the transmitter above the pressure tapping point.
Installing/mounting 4.3 Installation (except level) 4.3.3 Fastening Fastening without the mounting bracket You can fasten the transmitter directly on the process connection. Fastening with the mounting bracket You can fasten the mounting bracket as follows: ● On a wall or a mounting frame using two screws ● On a vertical or horizontal mounting tube (Ø 50 to 60 mm) using a tube bracket Fasten the transmitter mounting bracket using the two screws provided.
Installing/mounting 4.
Installing/mounting 4.4 "Level" installation Figure 4-3 An example of fastening on the mounting bracket in the case of differential pressure and vertical differential pressure lines 4.4 "Level" installation 4.4.1 Instructions for level installation Requirements Note Compare the desired operating data with the data on the nameplate. Please also refer to the information on the remote seal if this is fitted.
Installing/mounting 4.4 "Level" installation Note Protect the transmitter from: ● Direct heat ● Rapid temperature changes ● Severe soiling ● Mechanical damage ● Direct sunlight Note Select the height of the mounting flange such that the pressure transmitter is always mounted below the lowest fill height to be measured. The installation location is to be as follows: ● Easily accessible ● The measuring point must be as close as possible ● Vibration-free ● Within the permitted ambient temperature values 4.4.
Installing/mounting 4.4 "Level" installation 4.4.3 Connection of the negative pressure line Assembly on an open container A line is not required when taking measurements in an open container since the negative chamber is connected with the atmosphere. Ensure that no dirt enters the open connection ports, for example by using connection screws with a 7MF4997-1CP bleed valve.
Installing/mounting 4.4 "Level" installation Assembly on a closed container When taking measurements in a closed container without or with little condensate formation, the negative pressure line is not filled. Lay the line in such a way that pockets of condensate do not form. Install a condensation container if required.
Installing/mounting 4.
Installing/mounting 4.5 "Remote seal" installation ● Never loosen the sealed filling screws on the remote seal and the measuring instrument. ● Do not cause damage to the remote separating membrane; scratches on the remote separating membrane, e.g. due to sharp-edged objects, are the main starting points for corrosion. ● Select suitable gaskets for sealing. ● Use a gasket having an adequately large inner diameter for flanging.
Installing/mounting 4.5 "Remote seal" installation 4.5.2 Installation of the remote seal with the capillary line Notes ● Do not rest the measurement assembly on the capillary line. ● Do not bend capillary lines; risk of leakages and/or risk of considerable increase in the setting time of the measuring system. ● Owing to the risk of bending and breakages, pay attention to mechanical overloads at the joints such as capillary line-remote seal and capillary line-measuring device.
Installing/mounting 4.5 "Remote seal" installation +R Start of scale value: pMA = ρFL * g * HU - ρoil * g * H1 Full-scale value: pME = ρFL * g * HO - ρoil * g * H1 + +X + Pressure transmitter below the measuring point H1 ≤ 7 m (23 ft); with halocarbon oil as the filling liquid, only H1 ≤ 4 m(13.
Installing/mounting 4.5 "Remote seal" installation SDEV + Pressure transmitter for absolute pressure always below the measuring point: H1 ≥ 200 mm (7.
Installing/mounting 4.
Installing/mounting 4.5 "Remote seal" installation Key pMA pME ρFL ρoil g HU HO HV Start of scale value Full-scale value Density of the process medium in the container Density of the filling oil in the capillary line of the remote seal Acceleration due to gravity Lower filling level Upper filling level Gland distance Installation type G + +9 + + H1 ≤ 7 m (23 ft), for halocarbon oil, however only H1 ≤ 4 m (13.
Installing/mounting 4.6 Turing the measuring cell against housing Installation type J H2 ≤ 7 m (23 ft); with halocarbon oil as the filling liquid, only H2 ≤ 4 m(13.1 ft) Start of scale value: pMA = ρFL * g * HU - ρoil * g * HV Full-scale value: pME = ρFL * g * HO - ρoil * g * HV + + Between the measuring points, no vacuum Key pMA pME ρFL ρoil g HU HO HV 4.
Installing/mounting 4.7 Rotating the display ① ② ③ Turning range Retaining screw Orientation mark Figure 4-4 Example: turning range of transmitters for pressure and absolute pressure from the gauge pressure series The turning range for transmitters for differential pressure and flow rate, absolute pressure from the differential pressure series and level is identified in a similar manner.
Installing/mounting 4.7 Rotating the display 3. Screw the covers back on as far as they will go. 4. Secure the covers with the cover catch.
5 Connecting 5.1 Basic safety instructions 5.1.1 Unsuitable cables and/or cable glands WARNING Unsuitable cables and/or cable glands Danger of explosion in hazardous areas. ● Only use suitable cables and cable glands complying with the requirements specified in Chapter "Technical data (Page 169)". ● Tighten the cable glands in accordance with the torques specified in Chapter "Technical data (Page 169)". ● When replacing cable glands use only cable glands of the same type.
Connecting 5.1 Basic safety instructions WARNING Unsafe extra-low voltage Danger of explosion in hazardous areas due to voltage flashover. ● Connect the device to an extra-low voltage with safe isolation (SELV). WARNING Lack of equipotential bonding Danger of explosion through compensating currents or ignition currents through lack of equipotential bonding. ● Ensure that the device is potentially equalized.
Connecting 5.1 Basic safety instructions WARNING Connecting device in energized state Danger of explosion in hazardous areas. ● Connect devices in hazardous areas only in a de-energized state. Exceptions: ● Circuits of limited energy may also be connected in the energized state in hazardous areas.
Connecting 5.2 Connecting the device Note Electromagnetic compatibility (EMC) You can use this device in industrial environments, households and small businesses. For metal housings there is an increased electromagnetic compatibility compared to highfrequency radiation. This protection can be increased by grounding the housing, see Chapter "Connecting the device (Page 60)". Note Improvement of interference immunity ● Lay signal cables separate from cables with voltages > 60 V.
Connecting 5.2 Connecting the device 3. Connect the wires to the terminals "+" and "-". ④ Observe the correct polarity. If necessary, ground the device using the "-" connection by connecting the "‑" connection to the ground terminal ⑨. 4. If necessary, connect the shield to the screw of the ground terminal ⑨. The ground terminal is electrically connected to the external protective conductor connection.
Connecting 5.3 Connecting the Han plug 3. Close the key cover ①. 4. Tighten the screws in the key cover. 5. Check the tightness of the blanking plugs ⑤ and cable gland ② in accordance with the degree of protection.
Connecting 5.4 Connecting the M12 connector Procedure 1. Slide the sleeve and the screwed joint on the cable. 2. Strip approx. 8 mm of the cable ends. 3. Crimp the contact parts on the cable ends. 4. Assemble the coupling socket. IA UH Output current Auxiliary power ,$ 8+ Connector pin assignment with Han 7D or Han 8D plug 5.4 Connecting the M12 connector Procedure CAUTION A conductive connection must not exist between the shield and the connector housing.
Connecting 5.4 Connecting the M12 connector 6. Screw the cable ends and the shield in the pin insert. 7. Fix the parts of the cable jack as described by the connector manufacturer.
6 Operation 6.1 Overview of operation Introduction The following description contains an overview of the operating functions that you can execute using the pressure transmitter, and the safety notes that are to be observed when doing so. You can operate the transmitter on-site through HART communication. First, the on-site operation and then, the operating functions using HART are described.
Operation 6.3 Instructions for operation Function Using buttons Using HART Characteristic curve (lin., rad.) (Not relevant for absolute and gauge pressure) Yes Yes Customized characteristic curve No Yes Diagnostic function No Yes More operating functions for special applications are accessible through HART. If a device does not have a display, its operations are limited. This is however not applicable for selecting functions using HART. 6.
Operation 6.4 Display 6.4 Display 6.4.
Operation 6.4 Display 6.4.2 Units display Description The unit display comprises five 14-segment fields for representing the unit as a percentage value, physical unit or current value. A bar graph showing the percentage measured value range from 0 to 100% can be displayed as an alternative to the unit. The bar graph function is disabled by default.
Operation 6.4 Display 6.4.3 Error display Description If hardware faults, software errors or diagnostic alarms occur in the transmitter, the message "Error" appears in the measured value display. A ticker appears in the bottom line of the display indicating the type of error. This diagnostic information is also available via HART communication. Display Figure 6-3 Example of error message The following messages may appear as a ticker in the bottom line of the display.
Operation 6.4 Display 6.4.4 Mode display Description The selected active mode is shown in the mode display. Display Figure 6-4 Example for mode display In the example, a damping of 0.2 seconds was set in mode 4. 6.4.5 Status display Description The arrows of the status display have a different meaning depending on the mode setting. The table below shows the meanings of the arrows in the respective functions.
Operation 6.
Operation 6.5 Local operation See also Fault current (Page 118) Setting the current limits (Page 119) 6.5 Local operation 6.5.1 Local control elements Introduction The transmitter can be operated on-site using the keys. Selectable modes can be used to choose and execute the functions described in the table. The number of available functions is limited if the device does not have a display.
Operation 6.5 Local operation Operating functions Note Zero point calibration For absolute pressure transmitters, the start of scale value is at vacuum. A zero point calibration with transmitters which do not measure absolute pressure leads to faulty settings. Table 6-4 Operating functions using keys Function Mode Key function [M] [↑] Display, explanations [↓] [↑] and [↓] Measured value The modes are select ed here.
Operation 6.5 Local operation Function Key lock or function lock Characteristic curve1) Mode Key function [M] [↑] 10 Switch between the five functions 11 Display, explanations [↓] Switch between the four functions Smaller [↑] and [↓] – linear Application point of 12 the square root extracting characteristic curve1) Greater Measured value display 13 Select from three options.
Operation 6.5 Local operation Procedure In the default setting, the device is in the measured value display. To adjust the operating functions, proceed as follows: 1. Loosen both the screws of the keyboard cover and lift it upwards. 2. Keep pressing the [M] button until the desired mode is displayed. 3. Keep pressing the [↑] or [↓] button until the desired value is displayed. 4. Press the [M] button. Now you have saved the values and the device goes to the next mode. 5.
Operation 6.5 Local operation Depending on the series and measuring range, a maximum downscaling of 1:100 can be achieved (measuring span ratio = r, turn down). The correlation between the measured pressure and the output current generated is linear. The square root extracting characteristic curve for differential pressure transmitters is an exception. Calculate the output current using the following formula.
Operation 6.5 Local operation C 14 bar process pressure is created. Use the [M] button to set the transmitter to mode 3. To set the full scale value, press the [↑] and [↓] buttons simultaneously for 2 seconds. If there is 14 bar input pressure, the transmitter produces an output current of 20 mA. D The output current can be calculated for any input pressure using the "current calculation formula for setting".
Operation 6.
Operation 6.5 Local operation 6.5.3.2 Setting/adjusting the start of scale value NOTICE Inadvertent adjustment of parameters on devices without display or without visible display Key lock is canceled if you press the [M] key for longer than 5 seconds, see chapter "Releasing key lock or function lock (Page 91)". In the case of a device without display or without a visible display, you could inadvertently change parameters. ● Always press the [M] key for less than 5 seconds.
Operation 6.5 Local operation Setting the start-of-scale value without a display You have a device with a cover that does not have an inspection window and you wish to set the start of scale value. To set the output current of the start of scale value to 4 mA, proceed as follows: 1. Create the reference pressure. 2. Press the [↑] and [↓] buttons simultaneously. The device has set the start of scale value to 4 mA. 3. When you release the buttons, the device saves the adjusted value automatically.
Operation 6.5 Local operation 3. Set the full scale value to 20 mA. 4. Save with the [M] button. Adjusting full scale value If you do not set the output current but constantly adjust it, you need to calculate the currents to be adjusted mathematically. To the adjust the output current of the full scale value, proceed as follows: 1. Create the reference pressure. 2. Set mode 3. 3. Adjust the output current of the full scale value to the calculated value. 4. Save with the [M] button.
Operation 6.5 Local operation 6.5.4 Setting/adjusting electrical damping Difference between setting and adjusting You can set or adjust the time constant of electrical damping using the buttons. Setting means that the time constant is automatically set to 0 seconds. Adjusting means that the time constant is adjusted between 0 and 100 seconds using the steps of 0.1 seconds. This electrical damping also has an effect on the built-in basic damping of the device.
Operation 6.5 Local operation 6.5.5 Blind start of scale value/full scale value 6.5.5.1 Difference between setting/adjusting and blind setting/adjusting Differences In contrast to setting/adjusting with a reference pressure, you do not need a reference pressure for blind setting/adjusting. You can adjust a value in the physical variable "pressure" without a reference pressure, and an output current with a reference pressure. Blind adjusting First select the desired physical unit.
Operation 6.5 Local operation Explanations for the blind adjusting example A The measuring range is from 0 to 16 bar. You are changing the start of scale value from 0 to 2 bar and the full scale value from 16 to 14 bar. The measuring span is then 12 bar. In this example you create no pressure. B Use the [M] button to switch the transmitter to mode 5. To adjust the start of scale value to 2 bar, press one of the [↑] or [↓] buttons.
Operation 6.5 Local operation Condition You are familiar with the correct operation of the transmitter and the associated safety notes. You have not created any reference pressure and have selected a pressure unit. Procedure To the set the start of scale value blindly, proceed as follows: 1. Set mode 5. 2. Press the [↑] and [↓] buttons simultaneously for 2 seconds. 6.5.5.3 Blind setting of full scale value Introduction Blind setting resets the full scale value to the upper sensor limit.
Operation 6.5 Local operation 6.5.5.4 Blind adjusting of the start of scale value Introduction In the case of blind adjustment, adjust the pressure value of the start of scale value continuously and without a reference pressure. Note Changes in modes 5 and 6 have an exclusive effect on pressure scaling. This does not affect the scaling for level or customized characteristic curve. Therefore, only measured pressure values and pressure units are displayed in these modes.
Operation 6.5 Local operation Condition You are familiar with the correct operation of the transmitter and the associated safety notes. You have not created any reference pressure and have selected a pressure unit. Procedure To the adjust the pressure value of the full scale value blindly, proceed as follows: 1. Set mode 6. 2. Adjust the pressure value of the full scale value. 3. Save with the [M] button. 6.5.6 Trimming the zero point Introduction The zero point is calibrated in mode 7.
Operation 6.5 Local operation 1. Create the reference pressure. 2. Set mode 7. 3. Set the reference pressure on the display. 4. Save using the [M] key. 6.5.7 Current transmitter Introduction In mode 8, switch the pressure transmitter into the constant current operation. You can connect an external current transmitter in the constant current operation. The current then no longer corresponds to the process variable. The following output current can be adjusted irrespective of the input pressure: ● 3.
Operation 6.5 Local operation 6.5.8 Output current in case of fault Introduction When a fault occurs, the upper fault current is displayed in the basic setting. In mode 9, you can choose between the output of the upper and lower fault current. The standard values 3.6 mA and 22.8 mA are set. The standard values of the upper and lower fault current can be changed via HART communication. Condition You are familiar with the correct operation of the transmitter and the associated safety notes.
Operation 6.5 Local operation 6.5.9 buttons and function lock Introduction In mode 10, you can disable the functions that can be executed using buttons. Application example for a lock is e.g. safeguarding the saved parameters. Lock options You have the following lock options on the pressure transmitter: Table 6-5 Meaning of lock modes Lock mode Meaning 0 The device can be operated by means of the keys and HART communication. LA Keys on the transmitter are locked.
Operation 6.5 Local operation Condition You are familiar with the correct operation of the transmitter and the associated safety notes. Note In the measured value display function, check whether the desired setting is displayed. Procedure To disable the buttons, proceed as follows: 1. Set mode 10. 2. Select the desired lock mode. 3. Confirm the lock mode with the [M] button. 6.5.
Operation 6.
Operation 6.5 Local operation 2XWSXW > @ The dotted rectangle has been magnified in the form of the following characteristic curves in order to show the behavior of characteristic curves.
Operation 6.5 Local operation 6.5.12 Measured value display Note To use the operating functions with the buttons, first set the device variable (DV) parameters with a host system such as SIMATIC PDM. You will finds details of the relation between primary variable (PV) assignment and the DV in the following section: Measuring mode "Pressure" (Page 101) Introduction In mode 13, adjust the following types of measured value display: ● mA ● % ● Display of the PV selected via HART.
Operation 6.5 Local operation See also Measured value display (Page 121) 6.5.13 Unit Introduction In mode 14, select the physical unit in which the measured value display of the device should be shown. Condition You are familiar with the correct operation of the transmitter and the associated safety notes. You have already selected the desired measured value display via HART. Procedure To adjust the physical unit, proceed as follows: 1. Set mode 14. 2. Select a unit.
Operation 6.
Operation 6.
Operating functions through HART 7.1 7 Operating functions through HART communication Condition You can operate the transmitter through HART communication. The following is required for this purpose: ● A HART communicator or PC software such as SIMATIC PDM. ● A HART modem to connect a PC with the transmitter or a lead to connect a HART communicator with the transmitter. Introduction The full functionality of the transmitter is available via HART communication.
Operating functions through HART 7.3 Selecting the measuring modes 7.2 Process tag data You can store your process tag data in user definable fields.
Operating functions through HART 7.3 Selecting the measuring modes The following device variables are activated only when the allocated measuring mode is activated and parameterized simultaneously: ● "Level", "Volume" and "Mass" are allocated to the "Level" measuring mode. ● "Volumetric flow" and "Mass flow rate" are classified as "Flow rate" measuring mode. ● "User" is allocated to the "User" measuring mode. The inactive device variables have the CONSTANT status. 7.3.
Operating functions through HART 7.3 Selecting the measuring modes four variables, all other device variables are marked as inactive and have the CONSTANT status. These four variables are mapped with dynamic variables PV, SV, TV and QV by default. Switching an inactive device variable to the primary variable (PV) generates an error message since the variable currently does not have a valid measured value. This message is displayed in SIMATIC PDM or the HART communicator.
Operating functions through HART 7.3 Selecting the measuring modes In the device, the characteristic curve vertices are only provided once in the EEPROM. Therefore, if the measuring mode is changed, you will usually need to adjust the characteristic curve accordingly. The characteristic curve function expects at least two and at the most 30 characteristic curve vertices as input parameters. Characteristic curve vertices are entered in pairs of values x %;y %.
Operating functions through HART 7.3 Selecting the measuring modes with appropriate parameters. Only then will you be given a meaningful measured value for the three device variables.
Operating functions through HART 7.
Operating functions through HART 7.3 Selecting the measuring modes 7.3.7 Measuring mode "Flow rate" Description When you activate the "Flow rate" measuring mode, only two other device variables are active: volumetric flow and mass flow rate. If another block was active earlier, the corresponding device variables remain inactive and have the "CONSTANT" status. The "Flow rate" block here represents a series of permanently interconnected functions which you need to configure with appropriate parameters.
Operating functions through HART 7.3 Selecting the measuring modes Note When using the "Flow rate" block, other square root extracting characteristic curves must be deactivated if required.
Operating functions through HART 7.3 Selecting the measuring modes 7.3.8 Measuring mode "User" Description The "User" measuring mode is the simplest of the measuring modes that you can select with the measuring mode selector. Only one further device variable, "User", is activated in this measuring mode in addition to the four standard device variables. The variables "Level", "Volume", "Mass", "Volumetric flow" and "Mass flow rate" are marked as inactive and are given the status CONSTANT.
Operating functions through HART 7.
Operating functions through HART 7.3 Selecting the measuring modes characteristic curve vertices. These curve shapes can be stored in the device using SIMATIC PDM or the HART communicator. In the calculation example, the value at the input of the characteristic curve is transferred 1:1 to the output. In the calculation example, a number of filled cans is set for the output scaling. You can enter up to five characters for any given unit.
Operating functions through HART 7.3 Selecting the measuring modes The basic measured values, namely pressure and temperatures, have the BAD status in the following cases: ● The analog-to-digital converter does not function. ● Linearization values in the EEPROM are defective. ● If the two end points of the customized characteristic curve are exceeded for the status of the device variables of the following function.
Operating functions through HART 7.
Operating functions through HART 7.
Operating functions through HART 7.3 Selecting the measuring modes 7.3.10 Analog output Introduction The "Analog output" block converts the value provided by the dynamic primary variable (PV) into a current value of 4 to 20 mA. When you actuate the measuring mode selector, you automatically define the start of scale value and the full scale value to the current values 4 and 20 mA, respectively. Limit values of corresponding device variables are used for scaling the analog output by default.
Operating functions through HART 7.
Operating functions through HART 7.4 Setting zero point and limit point Example In the Level measuring mode, the start of scale value is assumed as 0 m and the full scale value as 10 m in the example illustrated in the following picture. The value of 2 m is displayed at a process pressure of 0.4 bar.
Operating functions through HART 7.6 Zero point calibration (position correction) 7.5 Blind setting of zero point and limit point ● The start of scale value and the full scale value can be set without creating a reference pressure. ● Both values can be selected as any point within the sensor limits. ● The maximum downscaling is 1:100, depending on the series and the measuring range. 7.
Operating functions through HART 7.10 Fault current 7.7 Electrical damping Description You can set the time constant of electrical damping to a point within a range from 0 to 100 s. It always applies to the "Pressure" device variable (DV0) and thus to the measured values derived from it. 7.8 Fast response mode Description This mode is only intended for special applications such as fast recognition of jumps in pressure, e.g. pressure drop in the event of pipe breakage.
Operating functions through HART 7.11 Setting the current limits See also Error display (Page 69) Limit modules (Page 131) 7.11 Setting the current limits Description The level of the upper and lower fault current and the upper and lower saturation limits can be freely selected within the preset limits of the current output signal. The specified accuracy of the current output signal is only valid within the current limits 4 to 20 mA.
Operating functions through HART 7.12 Key lock and write protection 7.12 Key lock and write protection Introduction You can use this function to lock the keys or activate write protection to safeguard the saved parameters. Lock options You have the following lock options: Table 7-3 Meaning of the HART lock modes Lock mode Meaning 0 The device can be operated by means of the keys and HART communication. LA Keys on the transmitter are locked.
Operating functions through HART 7.13 Measured value display 7.
Operating functions through HART 7.14 Selection of the physical unit ● If the pressure unit is < 5 characters, an A or a G is added at the end, respectively. ● If the pressure unit is ≥ 5 characters, the letters GAUGE or ABS flash alternately with the pressure unit. Figure 7-13 Add-on with example GAUGE Note The change of the display with GAUGE or ABS does not change the physical pressure used by the transmitter, rather only the nature of the display. See also Measured value display (Page 94) 7.
Operating functions through HART 7.16 Sensor calibration 7.15 Bar graph Description You can use this to switch on the "Bar graph" function in the device display as an alternative to the unit display. The "Bar graph" function is disabled in the factory state. See also Display elements (Page 67) 7.16 Sensor calibration 7.16.1 Sensor trim Description The sensor trim can be used to set the characteristic curve of the transmitter at two sensor trim points.
Operating functions through HART 7.17 Current sensor trim 7.16.2 Trimming the sensor Trim the sensor at the lower trim point The pressure at which the lower sensor trim is to be performed is applied at the transmitter. Via SIMATIC PDM or the HART Communicator, you instruct the transmitter to accept this pressure. This represents an offset shift of the characteristic curve.
Operating functions through HART 7.18 Factory calibration Example of an application The current is to be measured as a voltage drop from 1 to 5 V at a resistance of 250 Ohm +/5%. To trim the tolerance of the resistance, set the current transmitter so that the voltage drop at 4 mA is exactly 1 V and at 20 mA is exactly 5 V. ● Trim at 4 mA: Use the current transmitter trim menu option to instruct the transmitter to output 4 mA. Read the measured value at an ammeter and input it.
Operating functions through HART 7.19 Static configuration data Description You can use the menu-guided interface of SIMATIC PDM or HART Communicator to select the range of parameters to be reset: 1. Current trim 2. Sensor zero point calibration (position correction) 3. Pressure corrections (zero point calibration and sensor trim) 4.
Operating functions through HART 7.20 Flow rate measurement (only differential pressure) ● Sensor seal diaphragm material ● Transmitter model ● Housing material ● Tube length ● Process connection ● Electrical connection ● Process connection screw material ● Vent valve position For a series of these material data items, you can enter any designation of your choice under the option "Special".
Operating functions through HART 7.21 Diagnostic functions Variable application point The output current for the "srlin" and "sroff" functions can be displayed linearly or set to zero below the application point of the square root extracting characteristic curve. Fixed application point The "srlin2" function has a permanently defined application point of 10%. The range up to this point contains two linear characteristic curve sections. The first section ranges from the zero point to 0.
Operating functions through HART 7.21 Diagnostic functions required, refer to the attached table for operation of the HART Communicator or the help functions in the SIMATIC PDM software. 7.21.2 Operating hours counter Description An operating hours counter can be read via HART communication for the electronics and another for the sensor. For HART communication, use the HART Communicator or PC software such as SIMATIC PDM. The counters are activated the first time the transmitter is put into operation.
Operating functions through HART 7.21 Diagnostic functions When the warning/alarm limit has been reached, the following applies: 1. "Alarm/Acknowledge the request" resets the request / alarm message, but allows the timer to continue to run. In this state, a new alarm or warning is not possible since the time limits have already been exceeded. 2. "Reset timer" resets the request / alarm message, also resets the timer. It acknowledges the interrupt or warning at the same time.
Operating functions through HART 7.21 Diagnostic functions 7.21.5 Limit modules Introduction The diagnostic functions of this device give you an option to monitor the measured values in programmable limits. If the limits are not adhered to, the device sends a warning through HART communication or notifies a higher-level instance about an analog fault current. Monitoring of current saturation You can monitor the current output in the saturation range using a simple limit module.
Operating functions through HART 7.21 Diagnostic functions Example 1: the response time starts at t1. At t1, current reaches the configured saturation limit of 20.5 mA for the first time. At t2, the response time ends. The stop time begins and the interrupt is triggered. Time t3 is the configured end of the stop time. At t3, the interrupt is immediately revoked even if the current then drops below the saturation limit again.
Operating functions through HART 7.22 Simulation 7.22 Simulation 7.22.1 Overview of simulation Description With the "Simulation" diagnostic function, you can receive and process simulated measurement data onsite or in the control room without having process pressure or a temperature value. This allows you to run individual process sequences in the "cold" state and thus simulate process states.
Operating functions through HART 7.23 Limit monitor 7.22.2 Simulation as fixed value Description Taking the physical unit into account you can set a fixed simulation value for all three possible simulation paths. You can simulate the pressure value and both temperature values simultaneously. While pressure simulation is activated, the transmitter will not react to changes in the process pressure. The output value for the current adjusts itself in accordance with the preset pressure value.
Operating functions through HART 7.23 Limit monitor Hysteresis Operating point for chatter suppression in the case of small pressure changes. Response time The time which must pass after the limit is violated before this violation is registered. Stop time The time for which a limit interrupt or warning will always be sustained even when the event which triggered it is no longer present.
Operating functions through HART 7.23 Limit monitor Reset event counter upper limit Here you can reset the upper limit counter to zero. A new event is not possible until the counter has been reset. Reset event counter lower limit Here you can reset the lower limit counter to zero. A new event is not possible until the counter has been reset. Warning/interrupt acknowledgement Here you can acknowledge each warning or interrupt separately.
8 Functional safety 8.1 General safety instructions 8.1.1 Safety-instrumented system This chapter describes the functional safety in general and not specific to a device. The devices in the examples are selected as representative examples. The device-specific information follows in the next chapter. Description The combination of transmitter, automation system and final controlling element forms a safetyinstrumented system that performs a safety function.
Functional safety 8.1 General safety instructions Function principle of multi-channel operation Transmitter 6KXWGRZQ VLJQDO 0HDVXUHG YDOXH Figure 8-2 Final controlling elements Automation system Safety-instrumented system (SIL3) The transmitter generates process-related measured values that are transferred to the automation system. The automation system monitors these measured values.
Functional safety 8.1 General safety instructions The "average probability of dangerous failures of the entire safety-instrumented system" (PFDAVG) is normally split between the three sub-systems in the following figure.
Functional safety 8.2 Device-specific safety information for single-channel operation (SIL 2) 8.2 Device-specific safety information for single-channel operation (SIL 2) 8.2.1 Safety function Safety function for pressure transmitters The safety function of SITRANS P refers to the measurement of pressures. An additional safety accuracy of 2% of the measuring range (complete span) must be added to the applicationspecific measuring error for an output current of 4 to 20 mA.
Functional safety 8.2 Device-specific safety information for single-channel operation (SIL 2) Checking the safety function Note You should check the safety function while the device is mounted, if possible. If this is not possible, you can also check the safety function when the device is not mounted. Make sure that the transmitter is mounted in the same position for testing as it is in in the system. Note If the transmitter is locked in Mode 10, deactivate the lock to check the safety function.
Functional safety 8.2 Device-specific safety information for single-channel operation (SIL 2) ● Explosion protection for corresponding versions ● Electromagnetic compatibility in compliance with EN 61326 8.2.4 Behavior in case of faults Repairs Defective devices should be sent in to the repair department with details of the fault and the cause. When ordering replacement devices, please specify the serial number of the original device. You will find the serial number on the nameplate.
Functional safety 8.3 Device-specific safety information for redundant operation (SIL 3) ● The SITRANS P pressure transmitter is only used in applications with a low demand for the safety function (low demand mode). ● Communication with the HART protocol is used only for the following: – Device configuration – Reading diagnostics values – However, it is not used for operations critical to safety. In particular, the simulation function must not be activated in safety-related operation.
Functional safety 8.3 Device-specific safety information for redundant operation (SIL 3) Note Use of remote seals If remote seals are used, the application-specific measurement error is the product of the transmitter and remote seal measurement errors. WARNING Disregarding conditions for fulfilling the safety function Disregard can result in a malfunction of the process plant or application, e.g. process pressure too high, maximum level exceeded.
Functional safety 8.3 Device-specific safety information for redundant operation (SIL 3) The PLC program must monitor the measured values of both DS III devices. As soon as the measured values differ by e.g. 2% or more, the system must be brought into the safe state and the fault must be located. Note Switching-off of system at high monitoring accuracy The two transmitters are connected to the process at different positions.
Functional safety 8.3 Device-specific safety information for redundant operation (SIL 3) ● Check the measuring accuracy, which must be within the range of the application-specific measuring error for the safety function. – Set the measured value display to a unit of pressure in Mode 13. – Check the zero point, e.g. in a pressureless state, for gauge and differential pressure. – Check the zero point for absolute pressure, e.g. by applying a defined pressure.
Functional safety 8.4 Add-on parts Checking safety You should regularly check the safety function of the entire safety circuit in accordance with IEC 61508/61511. The testing intervals are determined in calculations for each individual safety circuit in a system (PFDAVG). Electronics and measuring cell The safety function of the transmitter is ensured only if you use the electronics, measuring cell, display and connection board delivered by the factory. These components cannot be replaced. 8.3.
Functional safety 8.4 Add-on parts WARNING Add-on parts unsuitable for process medium Danger of injury or damage to device. If the process medium is not suitable for the parts which come into contact with it, hot and/or toxic or corrosive substances could be released. ● Refer to the information in the chapter "Technical data (Page 169)". ● Make sure that the add-on parts are suitable for the corresponding application with regard to materials, temperature of process medium, and pressure. 8.4.
Commissioning 9.1 9 Basic safety instructions DANGER Toxic gases and liquids Danger of poisoning when the device is vented. If toxic process media are measured, toxic gases and liquids can be released when the device is vented. ● Before venting ensure that there are no toxic gases and liquids in the device. Take the appropriate safety measures. WARNING Improper commissioning in hazardous areas Device failure or danger of explosion in hazardous areas.
Commissioning 9.2 Introduction to commissioning Note Hot surfaces Hot process medium and high ambient temperatures lead to hot surfaces which can cause burns. ● Take corresponding protective measures, for example wear protective gloves. 9.2 Introduction to commissioning Following commissioning, the transmitter is immediately ready for use. To obtain stable measured values, the transmitter needs to be allowed to warm up for five minutes or so after the power supply is switched on.
Commissioning 9.3 gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge pressure series 9.3 gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge pressure series 9.3.
Commissioning 9.3 gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge pressure series Procedure To commission the transmitter for gases, proceed as follows: 1. Open the shut-off valve for the test connection ④. 2. Via the test connection of the shut-off fitting ②, apply the pressure corresponding to the start of scale value to the pressure transmitter ①. 3. Check the start of scale value. 4.
Commissioning 9.4 Differential pressure and flow rate Requirement All valves are closed. Procedure To commission the transmitter for steam or liquid, proceed as follows: 1. Open the shut-off valve for the test connection ④. 2. Via the test connection of the shut-off module ②, apply the pressure corresponding to the start of scale value to the pressure transmitter ①. 3. Check the start of scale value. 4. If the start of scale value differs from the value desired, correct it. 5.
Commissioning 9.4 Differential pressure and flow rate 9.4.
Commissioning 9.4 Differential pressure and flow rate 3. Open the differential pressure valve (③ or ④). 4. Check and if required correct the zero point when the start of scale value is 0 mbar (4 mA). 5. Close the stabilizing valve ②. 6. Open the other differential pressure valve (③ or ④). 9.4.
Commissioning 9.4 Differential pressure and flow rate Procedure WARNING The transmitter should not be depressurized if toxic substances are being used. To commission the transmitter with liquids, proceed as follows: 1. Open both the shut-off valves ⑥ at the pressure tapping point. 2. Open the equalizer valve ②. 3. With transmitters below the differential pressure transducer, open both the blowout valves one after the other ⑦ until the air-free liquid emerges.
Commissioning 9.4 Differential pressure and flow rate 9.4.4 Commissioning with vapor ① ② ③, ④ ⑤ ⑥ Differential pressure valves ⑦ ⑧ ⑨ Differential pressure transducer/Orifice plate Differential pressure lines ⑩ Insulation Pressure transmitter Stabilizing valve Drain valves Condensate pots Shut-off valves Figure 9-2 Measuring steam Condition All valves are closed.
Commissioning 9.4 Differential pressure and flow rate 3. Wait until the steam in the differential pressure lines ⑤ and in the equalizing vessels ⑧ has condensed. 4. Open the differential pressure valve ③ and the vent valve on the positive side of the transmitter ① slightly, until condensate escapes without bubbles. 5. Close the vent valve. 6. Open the vent valve on the negative side of the transmitter ① slightly, until condensate escapes without bubbles. 7. Close the differential pressure valve ③. 8.
Service and maintenance 10.1 10 Basic safety instructions WARNING Impermissible repair of explosion protected devices Danger of explosion in areas subject to explosion hazard. ● Repair must be carried out by Siemens authorized personnel only. WARNING Impermissible accessories and spare parts Danger of explosion in areas subject to explosion hazard. ● Only use original accessories or original spare parts.
Service and maintenance 10.1 Basic safety instructions WARNING Maintenance during continued operation in a hazardous area There is a danger of explosion when carrying out repairs and maintenance on the device in a hazardous area. ● Isolate the device from power. - or ● Ensure that the atmosphere is explosion-free (hot work permit). WARNING Commissioning and operation with pending error If an error message appears, correct operation in the process is no longer guaranteed.
Service and maintenance 10.1 Basic safety instructions WARNING Improper connection after maintenance Danger of explosion in areas subject to explosion hazard. ● Connect the device correctly after maintenance. ● Close the device after maintenance work. Refer to Chapter "Connecting (Page 57)". WARNING Use of a computer in a hazardous area If the interface to the computer is used in the hazardous area, there is a danger of explosion. ● Ensure that the atmosphere is explosion-free (hot work permit).
Service and maintenance 10.2 Maintenance and repair work NOTICE Electrostatic-sensitive devices The device contains electrostatic-sensitive devices (ESD). ESD can be destroyed by voltages far too low to be detected by humans. These voltages can occur if you simply touch a component part or the electrical connections of a module without being electrostatically discharged.
Service and maintenance 10.2 Maintenance and repair work 10.2.2 Checking the gaskets Inspect the seals at regular intervals Note Incorrect seal changes Incorrect measured values will be displayed. Changing the seals in a process flange of a differential pressure measuring cell can alter the start-of-scale value. ● Changing seals in devices with differential pressure measuring cells may only be carried out by personnel authorized by Siemens.
Service and maintenance 10.3 Cleaning In case of defect, you can replace the electronic unit by following the warning notes and the provided instruction manual. See also Error display (Page 69) 10.2.4 Changing the measuring cell and application electronics Related Each of the individual components "Measuring cell" and "Electronics" has a non-volatile memory (EEPROM). Measuring cell data (e.g.: measuring range, measuring cell material, oil filling) and applicationspecific electronics data (e.g.
Service and maintenance 10.3 Cleaning NOTICE Penetration of moisture into the device Device damage. ● Make sure when carrying out cleaning and maintenance work that no moisture penetrates the inside of the device. Cleaning the enclosure ● Clean the outside of the enclosure and the display window using a cloth moistened with water or a mild detergent. ● Do not use aggressive cleaning agents or solvents. Plastic components or painted surfaces could be damaged.
Service and maintenance 10.5 Disposal 10.4 Return procedure Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the outside of the packaging. Required forms ● Delivery note ● Return goods delivery note (http://www.siemens.
Service and maintenance 10.5 Disposal Note Special disposal required The device includes components that require special disposal. ● Dispose of the device properly and environmentally through a local waste disposal contractor.
Technical data 11.1 11 Overview of technical data Introduction The following overview of technical data provides you with a quick and easy access to relevant data and characteristic numbers. Remember that the tables partially contain the data of the three communication types HART, PROFIBUS and Foundation Fieldbus. This data deviates in many cases. Therefore, adhere to the communication type used by you when using the technical data.
Technical data 11.2 Input point 11.2 Input point Gauge pressure input HART PROFIBUS PA or Foundation Fieldbus Measured variable Gauge pressure Span (continuously adjustable) or measuring range, max. operating pressure (in accordance with 97/23/EC Pressure Equipment Directive) and max. test pressure (in accordance with DIN 16086) (max.
Technical data 11.2 Input point gauge pressure input, with flush mounted diaphragm HART PROFIBUS PA or Foundation Fieldbus Measured variable Gauge pressure Measuring span (continuously adjustable) or measuring range, max permissible operating pressure and max. permissible test pressure Span Maximum operating pressure MAWP (PS) Maximum test pressure Measuring range Maximum operating pressure Maximum test pressure 0.01 … 1 bar g (0.15 … 14.
Technical data 11.2 Input point Absolute pressure input, with flush-mounted diaphragm HART PROFIBUS PA or Foundation Fieldbus Lower measuring limit 0 bar a (0 psi a) Upper measuring limit 100% of maximum span 100 % of max. measuring range DS III input with PMC connection HART PROFIBUS PA or Foundation Fieldbus Measured variable Gauge pressure Measuring span (continuously adjustable) or measuring range, max permissible operating pressure and max.
Technical data 11.2 Input point Absolute pressure input (from the gauge pressure series) HART PROFIBUS PA or Foundation Fieldbus Measured variable Absolute pressure Measuring span (continuously adjustable) or measuring range, max permissible operating pressure (as per 97/23/ EC pressure device guideline) and max. permissible test pressure (as per DIN 16086) Span Maximum operating pressure MAWP (PS) Maximum test pressure Measuring range Maximum operating pressure Maximum test pressure 8.
Technical data 11.2 Input point Absolute pressure input (from the differential pressure series) HART PROFIBUS PA or Foundation Fieldbus Measured variable Absolute pressure Measuring span (continuously adjustable) or measuring range and max permissible operating pressure (as per 97/23/EC pressure device guideline) Span Maximum operating pressure MAWP (PS) Measuring range Maximum operating pressure 8.3 … 250 mbar a (3 ...
Technical data 11.2 Input point Differential pressure and flow rate input HART PROFIBUS PA or Foundation Fieldbus Measured variable Differential pressure and flow rate Measuring span (continuously adjustable) or measuring range and max permissible operating pressure (as per 97/23/EC pressure device guideline) Span Measuring range Maximum permissible operating pressure 1 … 20 mbar (0.4015 32 bar (464 psi) … 8.031 inH2O) 20 mbar (8.031 inH2O) 32 bar a (464 psi) 1 … 60 mbar (0.
Technical data 11.2 Input point Differential pressure and flow rate input HART for process temperature of -20°C < ϑ ≤ 60°C (-4°F < ϑ ≤ +140°F) PROFIBUS PA or Foundation Fieldbus -100% of max. measuring range (-33 % for 30 bar (435 psi) measuring cell) or 30 mbar a (0.44 psi a) ● -100% of max. measuring range (-33% for 30 bar (435 psi) measuring cell) for process temperature 60°C < ϑ ● 30 mbar a + 20 mbar a • (ϑ - 60 °C)/°C ≤ 100°C (max. 85°C (0.44 psi a + 0.
Technical data 11.4 Measuring accuracy 11.3 Output Output HART PROFIBUS PA or Foundation Fieldbus Output signal 4 … 20 mA Digital PROFIBUS-PA or Foundation Fieldbus signal ● Lower limit (continuously adjustable) 3.55 mA, set to 3.84 mA in the factory – ● Upper limit (continuously adjustable) 23 mA, set to 20.5 mA or optionally 22.0 mA in the factory – ● Ripple (without HART communication) ISS ≤ 0.5 % of the max.
Technical data 11.4 Measuring accuracy Measuring accuracy (as per EN 60770-1) gauge pressure HART PROFIBUS PA or Foundation Fieldbus Measurement deviation with cut-off point setting, including hysteresis and repeatability. Linear characteristic curve ≤ 0,075 % ● r ≤ 10 ≤ (0.0029 • r + 0.071) % – ● 10 < r ≤ 30 ≤ (0.0045 • r + 0.071) % – ● 30 < r ≤ 100 ≤ (0.005 • r + 0.
Technical data 11.4 Measuring accuracy Gauge pressure measuring accuracy, with flush mounted diaphragm HART PROFIBUS PA or Foundation Fieldbus ● r ≤ 10 ≤ (0.0029 • r + 0.071) % – ● 10 < r ≤ 30 ≤ (0.0045 • r + 0.071) % – ● 30 < r ≤ 100 ≤ (0.005 • r + 0.05) % – Settling time T63 without electrical damping Approx. 0.2 s Long-term drift at ±30° C (±54° F) In 5 years ≤ (0.25 • r) % Ambient temperature influence In percent ● At -10 … +60 °C (14 … 140 °F) ≤ (0.1 • r + 0.
Technical data 11.4 Measuring accuracy Measuring accuracy (as per EN 60770-1) DS III with PMC connection HART PROFIBUS PA or Foundation Fieldbus Long-term drift at ±30° C (±54° F) In 5 years ≤ (0.25 • r) % In 5 years ≤ 0.25% Ambient temperature influence In percent ● At -10 … +60 °C (14 … 140 °F) ≤ (0.08 • r + 0.1) % ≤ 0,3 % ● at -40 … -10°C and +60 … +85°C (-40 … 14°F and 140 … 185°F) ≤ (0.1 • r + 0.15) % per 10 K ≤ 0.
Technical data 11.4 Measuring accuracy Absolute pressure measuring accuracy (from gauge and differential pressure series) HART Influence of mounting position PROFIBUS PA or Foundation Fieldbus In pressure per change of angle ● for absolute pressure (from the gauge pressure series): 0.05 mbar (0.000725 psi) per 10° inclination ● for absolute pressure (from the differential pressure series): 0.7 mbar (0.
Technical data 11.4 Measuring accuracy Differential pressure and flow rate measuring accuracy HART PROFIBUS PA or Foundation Fieldbus Effect of the ambient temperature (double values for measuring cell 20 mbar g (0.29 psi g)) As percentage ● At -10 … +60°C (14 … 140°F) ≤ (0.08 • r + 0.1) % ≤ 0,3 % ● At -40 … -10°C and +60 … +85°C (-40 … 14°F and 140 … 185°F) ≤ (0.1 • r + 0.15) % per 10 K ≤ 0.25 % per 10 K ≤ (0.1 • r) % per 70 bar (1015 psi) ≤ 0.1% per 70 bar (1015 psi) Measuring cell 20 mbar (0.
Technical data 11.5 Operating conditions Level measuring accuracy HART PROFIBUS PA or Foundation Fieldbus ≤ (0.5 • r + 0.2) % ≤ 0,7 % Measuring cell 600 mbar (8.7 psi) ≤ (0.3 • r + 0.2) % ≤ 0,5 % Measuring cell 1.6 and 5 bar (23.2 and 72.5 psi) ≤ (0.25 • r + 0.2) % ≤ 0,45 % ≤ (0.25 • r + 0.15) %/10 K (≤ (0.25 • r + 0.15) %/18°F) ≤ 0.4 %/10 K (≤ 0.4 %/18°F) Measuring cell 600 mbar (8.7 psi) ≤ (0.15 • r + 0.15) %/10 K (≤ (0.15 • r + 0.15) %/18°F) ≤ 0.3 %/10 K (≤ 0.3 %/18°F) Measuring cell 1.
Technical data 11.
Technical data 11.5 Operating conditions Conditions of use for gauge pressure and absolute pressure with flush-mounted diaphragm ● Measuring cell with Neobee (FDA- -10 … +150°C (14 … 302 °F) compliant) -10 … +200°C (14 … 392 °F) with cooling extension ● Measuring cell with hightemperature oil filling 1) -10 ... +250 °C (14 ... 482 °F) with cooling extension Observe the temperature limits in the process connection standards (e.g.
Technical data 11.
Technical data 11.6 Construction 11.6 Construction Construction for gauge pressure and absolute pressure (from the gauge pressure series) Weight Approx. 1.5 kg (3.3 lb) for aluminum enclosure Material ● Wetted parts materials Process connection Stainless steel, mat. no. 1.4404/316L or Hastelloy C4, mat. no. 2.4610 Oval flange Stainless steel, mat. no. 1.4404/316L Seal diaphragm Stainless steel, material no. 1.4404/316L or Hastelloy C276, material no. 2.
Technical data 11.6 Construction Construction for gauge pressure, with flush mounted diaphragm Electronics housing ● Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.
Technical data 11.6 Construction DS III construction with PMC connection ● Standard ● Flush mounted ● 11/2'' ● PMC Standard design ● Minibolt ● Flush mounted ● 1'' ● PMC Minibolt design Electrical connection Cable inlet using the following cable glands: ● Pg 13.5 ● M20 x 1.5 ● ½-14 NPT ● Han 7D/Han 8D plug1) ● M12 connector Torque for cable gland nut made of 1) Plastic Metal Stainless steel 2.5 Nm (1.8 ft lb) 4.2 Nm (3.1 ft lb) 4.2 Nm (3.1 ft lb) Han 8D is identical to Han 8U.
Technical data 11.6 Construction Design for absolute pressure (from the differential pressure series), differential pressure and flow rate Electrical connection Screw terminals Cable inlet using the following cable glands: ● Pg 13.5 ● M20 x 1.5 ● ½-14 NPT or Han 7D/Han 8D connector1) ● M12 connector Torque for cable gland nut made of 1) Plastic Metal Stainless steel 2.5 Nm (1.8 ft lb) 4.2 Nm (3.1 ft lb) 4.2 Nm (3.1 ft lb) Han 8D is identical to Han 8U.
Technical data 11.7 Display, keyboard and auxiliary power Construction for level ● Mounting flange fill fluid Silicon oil or a different design Process connection ● Plus side Flange as per EN and ASME ● Minus side /4‑18 NPT female thread and flat connection with M10 fastening screw thread in accordance with DIN 19213 (M12 for PN 420 (MAWP 6092 psi)) or 7/16-20 UNF in accordance with EN 61518 Electrical connection Screw terminals 1 Cable inlet using the following cable glands: ● Pg 13.5 ● M20 x 1.
Technical data 11.8 Certificates and approvals Auxiliary power UH HART PROFIBUS PA or Foundation Fieldbus ● Max. basic current – 12.5 mA ● Starting current ≤ basic current – Yes ● Max. current in event of fault – 15.5 mA Error shut-down electronics (FDE) present – Yes 11.
Technical data 11.8 Certificates and approvals Certificates and approvals HART II 1 D IP65 T 120 °C, Marking PROFIBUS PA or Foundation Fieldbus II 1/2 D IP65 T 120 °C Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) max. surface temperature 120°C (248°F) Connection To a certified intrinsically safe circuit with the max. values: FISCO supply unit U0 = 17.5 V, I0 = 380 mA, P0 = 5.32 W Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Ω Linear barrier U0 = 24 V, I0 = 250 mA, P0 = 1.
Technical data 11.9 HART communication 11.9 HART communication HART communication Load for a 194 ● HART communicator connection 230 … 1100 Ω ● HART modem 230 … 500 Ω Cable 2-wire, shielded: ≤ 3.0 km (1.86 miles), multiwired, shielded: ≤ 1.5 km (0.93 miles) Protocol HART Version 5.
12 Dimension drawings 54 (2.13) 143 (5.6) 74 (2.9) 53 (2.1) 27 (1.1) 17 (0.67) 29 (1.14) 84 (3.31) 40 (1.57) 68 (2.68) 171 (6.73) 72 (2.8) 120 (4.72) 236 (9.29) 117 (4.61) 80 (3.15) ca. 96 (3.78) 50 (1.97) 15 (0.6) SITRANS P, DS III series for gauge pressure and absolute pressure from the gauge pressure series 24 (0.94) 12.1 123 (4.84) min. 90 min. (3.
Dimension drawings 12.1 SITRANS P, DS III series for gauge pressure and absolute pressure from the gauge pressure series ① ② ③ ④ Key cover Blanking plug Cover catch (only for "flameproof enclosure" type of protection) Electrical connection: ● Threaded joint Pg 13.5 (adapter)2)3), ● Threaded joint M20 x 1.
Dimension drawings 12.2 SITRANS P, DS III series for differential pressure, flow rate and absolute pressure from the differential pressure series 12.2 SITRANS P, DS III series for differential pressure, flow rate and absolute pressure from the differential pressure series 24 (0.94) 143 (5.6) 15 (0.6) 29 (1.14) 17 (0.67) 84 (3.31) 134 (5.28) min. 90 (3.54) 72 (2.83) 105 (4.
Dimension drawings 12.2 SITRANS P, DS III series for differential pressure, flow rate and absolute pressure from the differential pressure series ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ Key cover Blanking plug Cover catch (only for "flameproof enclosure" type of protection) Mounting bracket (optional) Lateral ventilation for gas measurement (addition H02) Sealing plug, with valve (optional) Lateral ventilation for liquid measurement Electrical connection: ● Pg 13.5 gland (adapter)2)3) ● M20 x 1.
Dimension drawings 12.2 SITRANS P, DS III series for differential pressure, flow rate and absolute pressure from the differential pressure series 143 (5.6) 53 (2.1) 24 50 (0.94) (1.97) 84 (3.31) ca. 217 (8.54) 29 (1.14) 17 (0.67) 80 (3.15) ca. 96 (3.78) 128 (5.04) 15 (0.6) min 90 (3.54) ca. 85 (3.35) 60 (2.36) 65 (2.56) ① ② ③ ④ ⑤ ⑥ ca. 87 (3.
Dimension drawings 12.3 SITRANS P, DS III series for level 12.3 SITRANS P, DS III series for level 177 (6.97) 29 (1.14) 84 (3.31) 53 (2.1) 143 (5.6) 74 (2.9) L 54 (2.1) min. 90 (3.54) d5 d4 166 (6.54) K D 15 (0.6) 108 (4.25) n x d2 ca. 96 (3.78) 17 (0.
Dimension drawings 12.3 SITRANS P, DS III series for level ① ② ③ ④ ⑤ Key cover Blanking plug Cover catch (only for "flameproof enclosure" type of protection) Process connection: Minus side 1/4-18 NPT (EN 61518) Electrical connection: ● Pg 13.5 gland (adapter)2)3) ● M20 x 1.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) 12.4 SITRANS P, DS III series (flush mounted) 143 (5.6) 53 (2.1) 15 (0.6) 84 (3.31) H 2 = ca. 55 (2.17) 29 (1.14) 24 (0.94) 50 (1.97) 74 (2.9) 80 (3.15) H1 = ca. 130 (5.12) 15 (0.6) min. 90 (3.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) 12.4.1 Note 3A and EHDG Note Approvals The references to the approvals for "EHEDG" and "3A" refer to the respective process connections and are not device-specific. Please refer to the technical data of the respective transmitter to see whether the desired certificate is available for your device/flange combination. 12.4.2 Connections as per EN and ASME Flange as per EN + EN 1092-1 ' DN PN ⊘D H2 25 40 115 mm (4.5'') Approx.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) Flanges as per ASME + ASME B 16.5 ' 12.4.3 DN CLASS ⊘D H2 Approx. 52 mm (2'') 1'' 150 110 mm (4.3'') 1'' 300 125 mm (4.9'') 1½'' 150 130 mm (5.1'') 1½'' 300 155 mm (6.1'') 2'' 150 150 mm (5.9'') 2'' 300 165 mm (6.5'') 3'' 150 190 mm (7.5'') 3'' 300 210 mm (8.1'') 4'' 150 230 mm (9.1'') 4'' 300 255 mm (10.0'') DN PN ⊘D H2 50 25 92 mm (3.6'') Approx. 52 mm (2'') 80 25 127 mm (5.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) + DIN 11864-2 Form A - sterile collar flange DN PN ⊘D H2 50 16 94 mm (3.7'') Approx. 52 mm (2'') 65 16 113 mm (4.4'') 80 16 133 mm (5.2'') 100 16 159 mm (6.3'') ' Approvals EHEDG + DIN 11864-2 Form A - sterile groove flange DN PN ⊘D H2 50 16 94 mm (3.7'') Approx. 52 mm (2'') 65 16 113 mm (4.4'') 80 16 133 mm (5.2'') 100 16 159 mm (6.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) Other connections Varivent® connector PN ⊘D H2 40-125 40 84 mm (3.3'') Approx. 52 mm (2'') DN PN ⊘D H2 65 40 105 mm (4.1'') Approx. 52 mm (2'') + DN ' Approvals EHEDG + Connection in accordance with DRD ' BioConnectTM connectors + BioConnectTM screwed joint ' Approvals 206 DN PN ⊘D H2 50 16 82 mm (3.2'') Approx. 52 mm (2'') 65 16 105 mm (4.1'') 80 16 115 mm (4.5'') 100 16 145 mm (5.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) + BioConnectTM flange connector ' Approvals DN PN ⊘D H2 50 16 110 mm (4.3'') Approx. 52 mm (2'') 65 16 140 mm (5.5'') 80 16 150 mm (5.9'') 100 16 175 mm (6.9'') 2" 16 100 mm (3.9'') 2½" 16 110 mm (4.3'') 3" 16 140 mm (5.5'') 4" 16 175 mm (6.9'') DN PN ⊘D H2 Approx. 52 mm (2'') EHEDG + BioConnectTM clamp connector ' Approvals 50 16 77.4 mm (3.0") 65 10 90.9 mm (3.6'') 80 10 106 mm (4.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) Other connections BioControlTM connector PN ⊘D H2 50 16 90 mm (3.5'') Approx. 52 mm (2'') 65 16 120 mm (4.7'') + DN ' Approvals 12.4.4 EHEDG PMC Style Connections for the paper industry PMC Style Standard DN PN ⊘D H2 – – 40.9 mm (1.6'') Approx. 36.8 mm (1.4'') + M44x1.25 cap nut ' PMC-Style Minibolt PN ⊘D H2 – – 26.3 mm (1.0'') Approx. 33.1 mm (1.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) 12.4.5 Special connections Tank connection TG52/50 and TG52/150 DN PN ⊘D H2 10 63 mm (2.5'') Approx. 63 mm (2.5'') 10 63 mm (2.5'') Approx. 170 mm (6.7'') DN PN ⊘D H2 2" 25 84 mm (3.3'') Approx. 52 mm (2.1'') 2½" 25 100 mm (3.9'') 3" 25 114 mm (4.5'') DN PN ⊘D H2 Approx. 52 mm (2.1'') TG52/50 43.5 mm TG52/150 + 43.
Dimension drawings 12.4 SITRANS P, DS III series (flush mounted) IDF connectors + IDF sockets with union nut DN PN ⊘D H2 Approx. 52 mm (2.1'') 2" 25 77 mm (3.0'') 2½" 25 91 mm (3.6'') 3" 25 106 mm (4.2'') DN PN ⊘D H2 Approx. 52 mm (2.1'') ' + IDF threaded sockets 2" 25 64 mm (2.5'') 2½" 25 77.5 mm (3.1'') 3" 25 91 mm (3.
13 Spare parts/accessories 13.1 Order data In order to ensure that the ordering data you are using is not outdated, the latest ordering data is always available on the Internet: Process instrumentation catalog (http://www.siemens.com/processinstrumentation/catalogs) Selection and order data Order no. CD "sitrans p - pressure transmitters" with documentation in German/ English/French/Spanish/Italian, etc.
Spare parts/accessories 13.1 Order data Selection and order data Order no. For transmitter for absolute pressure (7MF423.-.....-..A., -..B. and -..D.) ● Made of steel 7MF4997-1AC ● Made of stainless steel 7MF4997-1AJ Mounting bracket and fastening parts For SITRANS P, Series DS III, DS III PA and DS III FF Differential pressure transmitter with flange thread ● Made of steel For thread M10 (7MF433.-... and 7MF443.-...) 7MF4997-1AD For thread M12 (7MF453.-...
Spare parts/accessories 13.2 Order data for SIMATIC PDM Selection and order data Order no.
A Appendix A.1 Certificate The certificates can be found on the enclosed CD and on the Internet under: Certificates (http://www.siemens.com/processinstrumentation/certificates) A.2 Literature and standards No.
Appendix A.3 Literature and catalogs No. Title Publisher Order no. /4/ Catalog ST 80 SIMATIC HMI operation and observation products Siemens AG E86060-K4680-A101-B4 /5/ Catalog IK PI Industrial Communication Siemens AG Internet address: IK PI Catalog (http:// www.automation.siemens.com/net/ html_76/support/printkatalog.
Appendix A.4 Overview of HART operating structure A.4 Overview of HART operating structure The following overview applies to the HART communicator operating structure. 2 Online 1 2 3 4 (PV meas) *) (PV) status Module type Identification 1 Operation Unit 2 Device 3 Basic Parameters 5 Config Inp/Outp 1 Quick-Setup & Meas.
Appendix A.4 Overview of HART operating structure continuance 5 Config Inp/Outp continuance 2 Input continuance 3 Meas Switch/Mapper continuance 6 (measurement) config e.g. Level 3 Volume scaling 6 (measurement) config e.g. Flow 1 Input scaling 2 Flow scaling 6 (measurement) config e.g. Customer 1 Input scaling 3 Customer scaling 7 Unser linearization if Level, Flow or Customer this is valid - otherwise not 4 Meas.
Appendix A.4 Overview of HART operating structure continuance 5 Config Inp/Outp continuance 4 Local Meter 5 Mech. Construction Mech = mechanical 4 LCD Settings 5 Bargraph 1 LCD Scaling, if On: 6 Access Control 1 Lokal keys control mode 2 Write protect 3 Set write protect --> M 1 No of electronic changes 2 Design 1 Sensor 2 Remote Seal 3 Process Connection 4 Electronic Connection 6 Certif & Approv 7 Diagnosis/Service 1 Explos.
Appendix A.5 Technical support A.5 Technical support Technical Support You can contact Technical Support for all IA and DT products: ● Via the Internet using the Support Request: Support request (http://www.siemens.com/automation/support-request) ● E-mail (mailto:support.automation@siemens.com) ● Phone: +49 (0) 911 895 7 222 ● Fax: +49 (0) 911 895 7 223 Further information about our technical support is available on the Internet at Technical Support (http://www.siemens.
B List of abbreviations List of abbreviations Table B-1 Units Abbreviation In full Meaning bar a bar absolute Pressure unit for absolute pressure bar g bar gauge Pressure unit for gauge pressure lb Pfund (engl.
List of abbreviations B.1 Functional safety Abbreviation Full term in English Meaning MooN "M out of N" voting Classification and description of the safety-instrumented system in terms of redundancy and the selection procedures used. A safety-instrumented system or part that consists of "N" independent channels. The channels are connected to each other in such a way that "M" channels are in each case sufficient for the device to perform the safety instrumented function.
Glossary ATEX ATEX is an abbreviation of the French term "Atmosphère explosible" (potentially explosive atmosphere). ATEX stands for both EC directives in the area of explosion protection: ATEX product directive 94/9/EC and ATEX operating directive 1999/92/EC. Auxiliary power supply Auxiliary power supply refers to an electrical supply or reference voltage which some electrical circuits require apart from the standard supply.
Glossary Fault → Failure/Fault Fault tolerance Fault tolerance N means that a device can execute the intended task even when N faults exist. The device fails to execute the intended function in case of N+1 faults. Final controlling element Converter that converts electrical signals into mechanical or other non-electrical variables. Firmware Firmware (FW) is software that is embedded on a chip in electronic devices – in contrast to software which is saved on hard disks, CD-ROMs or other media.
Glossary Non-volatile memory → EEPROM Risk The combination of probability of a damage occurring and its magnitude. Safety function Defined function executed by a safety-instrumented system with the objective of achieving or maintaining a safe system status taking into account a defined dangerous occurrence.
Glossary The achievable SIL is determined by the following safety characteristics: ● Average probability of dangerous failure of a safety function in case of demand (PFDAVG) ● Hardware fault tolerance (HFT) ● Safe failure fractions (SFF) srli2 → srlin2 srlin2 "srli2" or "srlin2" is a type of square root extracting characteristic curve for the output current.
Index PV Primary variable, 102 QV Quarternary variable, 102 SV Secondary variable , 102 TV Tertiary variable, 102 3 3A, 203 A Acknowledgement, 129 Additional Support, 220 Ambient temperature, 183, 184, 185, 186 Influence, 178, 179, 180, 182 Analog output, 114 Analog output block, 114 Analog output stage, 101 Appendix, 215 Approval 3A, 203 EHEDG, 203 Approval plate, 22 Arrow display, 70 B Bar graph, 123 Basic variables, 65 Blind adjustment, 117 Bridge output voltage, 25, 26, 27 C Calibration Current tran
Index F M Factory calibration, 125 Failure current, 118 Fast recording of measured values, 118 Fast Response Mode, 118 Filling liquid, 25, 27, 28 Final controlling element , 137 Firmware, 9 Firmware version Safety Integrity Level, 141, 144 Flange, 27, 44 Full-scale value Set, 75 Function chart, 29 M12 connector, 63 MA Start of scale value, 102 Maintenance, 142, 146 Mapper, 101, (Also see: Variable mapper) Mass, 104, 105 MAWP, 221 ME Full scale value, 102 Measured value display, 75, 94 Measured value sta
Index Pressure simulation, 134 Pressure unit, 122 Primary variable, 71, 94 Process connection, 20 PV Primary variable, 94 Q Qualified personnel, 14 R Ramp function, 133, 134 Remote seal Description, 31 Install, 47 Maintenance, 165 Response time, 131 Root application point, 92, 106 T Tank connection, 209 Technical data, 140, 145 Test certificates, 13 Transmitter, 137 Trimming lower trim point , 124 upper trim point, 124 Turning range, 54 V Variable mapper, 101 Vent valve, 127, 156, 158 Volume, 105 W Wr
www.siemens.com/processautomation Siemens AG Industry Automation (IA) Sensors and Communication Process Analytics 76181 KARLSRUHE DEUTSCHLAND Subject to change without prior notice A5E00047092-08 © Siemens AG 2012 www.siemens.