User's Manual

2-59
1010NFM-3J
Section 2
Assigning Io Output Functions
The Io analog output is a self-powered, isolated 4-20mA DC signal that varies linearly in relation to a
selected data function.
CAUTION: Do not connect to a powered loop.
To assign a function for the current output:
From [Analog Out Setup], press twice to access the [Io] option list.
To move the cursor to the desired data function press
To store selection press
ENT
NOTE: For Multi-Channel meters, refer to drawing 1010MN-7 for details. For Expanded I/O
modules, refer to drawing 1010N-7-7 and Addendum 1010FMA-14 for details.
Model Number and I/O Module Installation Drawing and Page Number*
1010N 1010N-2-7 (Sheet 2 of 2)
1010N with 1010N-7 Expanded I/O Module 1010N-7-7 (Sheet 2 of 3)
1010DN 1010N-2-7 (Sheet 2 of 2)
1010DN with 1010N-7 Expanded I/O Module 1010N-7-7 (Sheet 2 of 3)
Table To Determine Proper I/O Installation Drawings
*Note: For Ultra Precsion transducers see 1010N-7-7 (sheet 3 of 3).
Io (Isolated current) 4 to 20 mA varies in proportion to an assigned data function.
Vo (DC voltage) 0 to 10 Vdc varies in proportion to an assigned data function.
Pgen (TTL logic) 0 to 5000 Hz varies in proportion to an assigned data function.
System 1010 Analog Outputs
Vfo Spanned volumetric/mass flow rate
Vfab Spanned unsigned flow magnitude
Vs Spanned liquid sonic velocity
Valc Receive signal amplitude
Vaer Relative degree of liquid aeration/cavitation
Vsg Spaned specific gravity
Viscosity System liquid viscosity
T1 Current liquid temperature
Iin1, Iin2 Represents a re-transmit of the analog input signals (e.g.,
Pressure and Temp inputs can be transmitted on the 4/20
mA output.)
Iin3, Iin4 Same as Iin1 and Iin2 above but only available for opera-
tion in Multi-Beam and Arithmetic modes.
Analog Out Setup Data Categories