User's Manual
2-46
1010NFM-3JSection 2
High Flow
The [High Flow Alarm] menu cell allows you to set the HI Alarm relay trip-point and the position of the HI
Alarm cursor on the Stripchart Display. The entered value must fall within the volumetric flow (Vfo)
analog span for the HI Alarm cursor to appear on the Graphic Screen.
To set the High Flow Alarm:
To activate numeric entry press
Use numeric keys to type the High Flow Alarm setpoint in the selected flow rate units.
To store data press
Low Flow
The[ Low Flow] menu cell allows you to set the LO Alarm relay trip-point and position of the LO Alarm
cursor on the Stripchart Display. The entered value must fall within the volumetric flow (Vfo) analog
span for the Low Alarm cursor to appear on the Graphic Screen.
To set the Low Flow Alarm:
To activate numeric entry press
Use the numeric keys to type the Low Flow alarm setpoint.
To store data press
The following Alarm Relay Setpoints are set in the same way as the two previously shown examples by
entering numeric values and storing the data.
High S.G.
This selection sets the High S.G. alarm function the specific gravity of a selected liquid.
Low S.G.
This selection sets the Low S.G. alarm function the specific gravity of a selected liquid.
High Viscosity cS
The [High Viscosity cS] menu cell sets the high liquid viscosity alarm relay setpoint. The viscosity units
are centistokes with no alternatives offered.
Low Viscosity cS
The [Low Viscosity cS] menu cell sets the low liquid viscosity alarm relay setpoint. The viscosity units
are centistokes with no alternatives offered.
High Temperature
The [High Temperature] menu cell sets the high temperature alarm relay setpoint. If metric preferences
are selected prior to site creation the temperature units will be in Centigrade. If English preferences are
selected prior to site creation the temperature units will be in Fahrenheit.
Low Temperature
The [Low Temperature] menu cell sets the low temperature alarm relay setpoint If metric preferences
are selected prior to site creation the temperature units will be in Centigrade. If English preferences are
selected prior to site creation the temperature units will be in Fahrenheit.