User's Manual
2-35
1010NFM-3J
Section 2
2.5.1 DAMPING CONTROL
System 1010 provides two different data output filter types, SmartSlew and Time Average (recom-
mended). SmartSlew provides the best combination of data smoothing and quick response to sudden
rate changes. It performs data scatter damping during steady flow periods while maintaining the ability
to respond instantaneously to changing flow rates. SmartSlew values range from [1 to 9]. The default
is [6]. Pick a higher number to slow meter response to a rate change. Time Average integrates the
instantaneous flow rate over a selectable time period. You enter a value (in seconds), which sets the
time it takes the meter to respond to a rate change. The default is 10 seconds. Enter any amount of
time up to 60 seconds maximum.
To edit the default SmartSlew setting:
To access the [SmartSlew] option list press three times.
Scroll the numeric list to the desired choice press
To register the new value press
To select Time Average:
To access the [Damping Control] option list press
To move the cursor down to [Time Average] press
To enable Time Average entry press
Use the numeric keys to type the new Time Average setting.
To register the new value press
2.5.2 DEADBAND CONTROL
Use Deadband Control to instruct the meter to report zero flow if the flow rate falls below a specified
level (usually a very low rate). It will prevent the possibility of data scatter (a natural result of digital
computation) from causing false totalizer accumulation during long non-flowing periods. Inspect the
actual data scatter during zero flow conditions to find the proper deadband setting for your application.
To edit the default setting (0.000):
To enable numeric entry press
Use the numeric keys to type in the desired rate (using selected flow rate units).
To register the new value press
ENT
ENT
ENT
ENT
Operation Adjust Damping Control Smart Slew x (numeric selection)
Time Average xx.x (numeric entry)
Deadband Control x.xx (numeric entry)
Memory/Fault Set Memory
Fault
Memory Delay (sec) xxx (numeric entry) (hidden in Fault Mode)
Reflexor/Zero/Fault Set Fault/Zero (Reflexor Mode only)
OPERATION ADJUST MENU STRUCTURE