User's Manual
2-26
1010NFM-3JSection 2
Transducer Model 1011 Universal
Transducer Size B3
Xdcr Mount Mode Direct
Spacing Offset Minimum
Number Index 4
Spacing Method Track 1012TP
Ltn Value (in) 0.217
Install Completed? Yes
Empty Pipe Set Channel Not Setup
Zero Flow Adjust Channel Not Setup
Siemens 2 Channel [1] SITE1
Key [Install] after mounting transducers
Pick/Install Xdcr
Press <ENT>. The [Install Completed?] menu cell will indicate [Yes] after the 1010 is successfully
installed.
NOTE: If the transducers have been installed successfully but the Estimated Vs (sonic veloc-
ity) has been changed, the Pick/Install Xdcr menu cell [Install Completed?] option list
will also display the [Transfer Install] function selection. The Transfer Install function
allows the transducers to be optimally positioned for a different fluid, without the need
for a new Initial Makeup procedure (see the Water Calibration addendum in this manual
for details).
Transducer Model 1011 Universal
Transducer Size B3
Xdcr Mount Mode Direct
Spacing Offset Minimum
Number Index 4
Spacing Method Track 1012TP
Ltn Value (in) 0.217
Install Completed? No
Empty Pipe Set Channel Not Setup
Zero Flow Adjust Channel Not Setup
Siemens 2 Channel [1] SITE1
Key [Install] after mounting transducers
Pick/Install Xdcr
To complete the Install process proceed to page 2-27 and disregard the following paragraphs
explaining the Force Transmit and Force Frequency diagnostic software routines.
After transducers are properly mounted, the flow computer completes its Initial Makeup command and
the [Install Completed?] menu cell appears.
To access the [Install Completed?] option list, press the <Right Arrow>.
Press <Down Arrow> and scroll to the [Install Completed?] menu cell and then press <ENT>
(unless otherwise directed to do so by Controlotron’s Technical Service Department).