User's Manual
1-15
1010NFM-3JSection 1
1.8 USING FASTSTART SETUP
The dual-channel clamp-on mode offers a choice of using FastStart Setup or Full Site Setup to create
your site setup. As its name implies, FastStart Setup is a quick way to start up the meter. FastStart
inserts default settings into all applicable menu cells. However, these can be edited later via the Full
Site Setup menu. In order to use FastStart Setup:
z Your pipe must be included on the meter’s pre-set pipe table.
z Your liquid is water, or has similar sonic characteristics.
FastStart setup is actually a shortcut to these two menu locations (where data entry is mandatory for a
successful start-up):
z Pipe Data: The Pipe Data Menu is limited to the selection of pipe pre-sets only. There
are no provisions for manual pipe editing.
z Pick Install Xdcr: This is the same menu as Full Menu Setup (see paragraph 1.7).
Press to access the Pipe Class option list. Note that although [Manual Entry] exists on this
list, it is inactive for FastStart Setup (see paragraph 2.2.1).
1.8.1 CHOOSING THE PIPE CLASS/SIZE
Press to access [FastStart Setup]. This selects [Choose Pipe Class]. There are over sixty English
and metric pipe sizes for eight different classes of pipes. Picking a pipe class and size automatically
sets all the required pipe parameters using industry standard dimensional data.
In this example, we will pick the pipe class: [ASA Carbon Steel] by moving the cursor to the
selection and then pressing .
ENT
Siemens
Siemens