Electropneumatic Positioner Part Manual

Operation
141
SIP ART PS2 Manual
A5E00074631--06
MeasureMeaning/cause
Lower
line
Upper
line
UP > x UP” tolerance range exceeded or
inactive zone of the potentiometer
passed
S Increase effective lever length for
linear actuators or switch
transmission ratio selector to
90 degrees
S Press operating mode button briefly
to acknowledge
S Restart initialization
90_95 x Only possible for part-turn actuators:
Actuator travel is not within the range
of 90 to 95%
S Use the “+” and “--” buttons to move it
to the range between 90 and 95%
S Press operating mode button briefly
to acknowledge
U--d> x “Up-Down” measuring span fallen
short of
S Reduce effective lever length for
linear actuators or switch
transmission ratio selector to
33 degrees
S Press operating mode button briefly
to acknowledge
S Restart initialization
U nn.n
D-->U
x
x
Display of actuating time “Up” S Wait, or
S press the “-- button to interrupt the
initialization process to change the
actuating time,
or
S activate the leakage test with the “+”
button
d nn.n
U-->d
x
x
Display of the actuating time “Down” S Wait, or
S press the “-- button to interrupt the
initialization process to change the
actuating time,
or
S activate the leakage test with the “+”
button
NOZZL x Actuator stationary (initialization was
interrupted with the “--” button during
the indication of the actuating speed)
S Actuating time can be changed by
adjusting the reactor(s)
S press the “-- button to repeat the
determination of the actuating speed
S continue with the “+” button
TESt
LEAKG
x
x
Leakage test active (“+“ button was
pressed during the indication of the
actuating speed)
S Wait one minute
S continue with the “+” button
nn.n
_oMIN
x
x
Value and unit of the result after the
leakage test
S Eliminate if leakage value is too great
S continue with the “+” button
nn.n
FINSH
x
x
Initialization was completed
successfully, possibly along with the
indication of the actuator travel or
angle
S Press the operating mode button
briefly to acknowledge and exit the
configuration level by pressing it
continuously