Specifications

SINAMICS G150
Drive converter cabinet units
75 kW to 1500 kW
3/8
Siemens D 11 · 2008
3
Technical specifications
Deviations from the defined classes are identified by underlining
.
1)
The EN standard specified is the European edition of international
standard IEC 62103.
2)
The EN standards specified are the European editions of the interna-
tional IEC standards with the same designations.
Electrical data Single circuit Parallel circuit
Line voltages and
power ranges
380 ... 480 V 3 AC, $10 % (-15 % < 1 min) 110 ... 560 kW 630 ... 900 kW
500 ... 600 V 3 AC, $10 % (-15 % < 1 min) 110 ... 560 kW 630 ... 1000 kW
660 ... 690 V 3 AC, $10 % (-15 % < 1 min) 75 ... 800 kW 1000 ... 1500 kW
Types of supplies TN/TT systems or isolated systems (IT systems)
Line frequency 47 ... 63 H z
Output frequency 0 ... 300 H z
Power factor
- Fundamental mode > 0.98
- Total 0.93 ... 0.96
Converter efficiency > 98 %
Control method Vector Control with and without sensor or
V/f
control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable
(in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal
block/PROFIBUS)
Skipped speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital
12 bit analog
Braking operation Optional via braking unit
Mechanical data
Degree of protection IP20 (higher degrees of protection up to IP54 optional)
Protection class ' In accordance with EN 50178 Part 1
1)
Cooling method Forced air cooling AF in accordance with EN 60146
Sound pressure level
L
pA
(1 m)
" 72 dB at 50 H z line frequency " 75 dB
Shock protection BGV A3
Cabinet system Rittal TS 8, doors with double-barb lock, three-section base plates for cable entry
Paint finish RAL 7035 (indoor requirements)
Compliance with standards
Standards EN 50178
1)
EN 60146-1, EN 61800-2, EN 61800-3, EN 60204-1, EN 60529
2)
CE marking In accordance with EMC directive No. 2004/108/EC and low-voltage directive No. 2006/95/EC
EMC conformance The SINAMICS G150 converter systems are not designed for connection to the public power network
("First environment"). EMC conformance is compliant with the EMC product standard for variable-speed
drives EN 61800-3, "Second environment" (industrial networks). The equipment can cause electromag-
netic interference when it is connected to the public network. If supplementary measures are taken, (e.g.
line filters, # option L00), it can also be operated in the "First environment".
Ambient conditions Storage Transport Operation
Ambient temperature -25 ... +55 °C -25 ... +70 °C
from -40 °C for 24 hours
0 ... +40 °C
up to +50 °C see derating data
Relative humidity
2)
(non-condensing)
5 ... 95 % 5 ... 95 %
at 40 °C
5 ... 95 %
Class 1K4 to EN 60721-3-1 Class 2K3 to EN 60721-3-2 Class 3K3 to EN 60721-3-3
Environmental class/harmful chemical
substances
2)
Class 1C2 to EN 60721-3-1 Class 2C2 to EN 60721-3-2 Class 3C2 to EN 60721-3-3
Organic/biological influences
2)
Class 1B1 to EN 60721-3-1 Class 2B1 to EN 60721-3-2 Class 3B1 to EN 60721-3-3
Installation altitude Up to 2000 m above sea level without derating, > 2000 m see derating data
Strain resistance Storage Transport Operation
Vibratory load
2)
- Deflection 1.5 mm at 5 ... 9 H z 3.1 mm at 5 ... 9 H z 0.075 mm at 10 ... 58 H z
- Acceleration 5 m/s
2
at > 9 ... 200 H z 10 m/s
2
at > 9 ... 200 H z 10 m/s
2
at > 58 ... 200 H z
Class 1M2 to EN 60721-3-1 Class 2M2 to EN 60721-3-2
Shock load
2)
- Acceleration 40 m/s
2
at 22 ms 100 m/s
2
at 11 ms 100 m/s
2
at 11 ms
Class 1M2 to EN 60721-3-1 Class 2M2 to EN 60721-3-2 Class 3M4 to EN 60721-3-3
© Siemens AG 2008