Specifications

SINAMICS G150
Drive converter cabinet units
75 kW to 1500 kW
3/5
Siemens D 11 · 2008
3
Function
AOP30 Advanced Operator Panel
An AOP30 Advanced Operator Panel is located in the cabinet
door of the converter for operation, monitoring and commission-
ing tasks.
The AOP30’s two-stage safety concept prevents unintentional or
unauthorized changes to settings. Operation of the drive from
the operator panel can be disabled by a password ensuring that
only parameter values and process variables can be displayed
on the panel. The OFF key is factory-set to active but can also
be deactivated by the customer. A password can be used to pre-
vent the unauthorized modification of converter parameters.
The user is guided through the screens for commissioning the
drive by the menu-driven display. Only 6 motor parameters
(which can be found on the motor rating plate) have to be en-
tered when the AOP30 is commissioned for the first time. The
control is then optimized automatically to fine-tune the converter
to the motor.
English, French, German, Italian, Spanish and Chinese are
stored on the CU320 Control Unit’s CompactFlash card as oper-
ator panel languages. The desired language must be down-
loaded to the AOP30 prior to commissioning. Russian, Polish
and Czech are available in addition to these standard panel lan-
guages. These can be downloaded free of charge from the In-
ternet under the following link:
http://support.automation.siemens.com/
The following pictures show examples of plain-text displays in
various operating phases.
First commissioning is carried out using the operator panel.
Only 6 motor parameters have to be entered:
power, speed, current, cos phi, voltage and frequency of the
motor.
This information can be found on the motor rating plate and is
entered into the screens on the display by following a short,
menu-driven procedure. The cooling method of the motor must
be entered in addition.
The next screen contains the parameter values that are used to
automatically optimize the control.
During operation, current data are output on the display as ab-
solute values such as setpoint and actual values , or it is possible
to parameterize up to 3 process variables as a quasi-analog bar
display.
Any alarms which occur are signaled by flashing of the yellow
"ALARM" LED, faults by lighting up of the red "FAULT" LED.
There is also an indication of the cause displayed in plain text on
the display’s status line.
Service /Commissioning
Drive commissioning
Device commissioning
AOP settings
AOP diagnosis
Help
G_D011_en_00047
Back Select.
Motor data
Back
p0304 MOT.U_rated 400.0 V
p0305 MOT. I_rated 405.0 A
p0307 MOT.P_rated 235.0 kW
p0308 MOT.CosPhi_ rated 0.870
Help Change OK
G_D011_en_00048
G_D011_en_00049
Basic commissioning
Back
p0700 Pre-assignment BI S/G150 TM 32
p1000 Default DI n_set TM 31 AIO
p1080 Minimum speed 0.000 rpm
-1
p1082 Maximum speed 1500.000 rpm
-1
Help Change Further
Operation 12:25:30
Nset
Fout
M
P act
Nact:
1450.0 rpm
1450.00
48.50
2700
410
rpm
Hz
Nm
kW
1450.0 rpm
385.3 V
748
Nact
Imot
Vout
G_D011_EN_00011b
0% 50 100%
0% 50 100%
G_D011_EN_00012b
Operation 12:25:30
NSET 1465.50 rpm Pact 410 kW
Fout 48.50 Hz Vout 385.3 V
Imot
748 A
Nact
1465 rpm
(3 : Vector) Current fault in
F 07901 Motor overspeed
Help Alt Back Ack.
G_D011_en_00050
G_D011_en_00051
Motor overspeed
Fault val = 000000007 00000007 (hex)
Cause:
The maximum permisible positive or
negative speed has been exceeded.
The maximum permissile positive speed
is calculated as follows:
Back
© Siemens AG 2 0 0 8