Specifications

SINAMICS G150
Drive converter cabinet units
Conductor cross-sections and connections
3/39
Siemens D 11 · 2008
3
Overview (continued)
Parallel circuit
Note
: The recommended and maximum conductor cross-sections relate to the
appropriate subsystem of the converter connected in parallel circuit.
1)
The recommendations for the North American market in AWG or MCM
must be taken from the appropriate NEC (National Electrical Code)
or CEC (Canadian Electrical Code) standards.
Type
rating
Converter Weight Line connection Motor connection Cabinet grounding
SINAMICS G150
Version A
(standard
version)
Recom-
mended
cross-
section
1)
Maximum
conductor
cross-
section
Fixing
screw
M12
Recom-
mended
cross-
section
1)
Maximum
conductor
cross-
section
Fixing
screw
M12
Fixing
screw
M12
Comment
DIN VDE DIN VDE (Number
of holes)
DIN VDE DIN VDE (Number
of holes)
(Number
of holes)
kW 6SL3710- ... kg mm
2
mm
2
mm
2
mm
2
380 ... 480 V 3 AC
630 2GE41-1AA0 1700 2x240 4x240 (2) 2x185 4x240 (2) (2)
710 2GE41-4AA0 1710 3x185 4x240 (2) 3x150 4x240 (2) (10) ground bus
900 2GE41-6AA0 2130 4x150 8x240 (4) 3x185 4x240 (2) (16) ground bus
500 ... 600 V 3 AC
630 2GF38-6AA0 1700 2x185 4x240 (2) 2x150 4x240 (2) (2)
710 2GF41-1AA0 1700 2x240 4x240 (2) 2x185 4x240 (2) (2)
1000 2GF41-4AA0 2620 3x185 8x240 (4) 3x150 6x240 (3) (18) ground bus
660 ... 690 V 3 AC
1000 2GH41-1AA0 1700 2x240 4x240 (2) 2x185 4x240 (2) (2)
1350 2GH41-4AA0 2620 3x185 8x240 (4) 3x150 6x240 (3) (18) ground bus
1500 2GH41-5AA0 2700 4x150 8x240 (4) 3x185 6x240 (3) (18) ground bus
© Siemens AG 2008