The tables below show the recommended or maximum possible
conductor cross-sections on the line and motor sides.
The recommended cross-sections are based on the listed fuses
and single routing of the three-wire cables at an ambient temper-
ature of 40 °C.
When the conditions differ from the above stated (cable routing,
cable grouping, ambient temperature), the instructions for rout-
ing the cables must be taken into account.
Single circuit
1)
The recommendations for the North American market in AWG or MCM
must be taken from the appropriate NEC (National Electrical Code)
or CEC (Canadian Electrical Code) standards.
Type
rating
Converter Weight Line connection Motor connection Cabinet grounding
SINAMICS G150
Version A
(standard
version)
Recom-
mended
cross-
section
1)
Maximum
conductor
cross-
section
Fixing
screw
M12
Recom-
mended
cross-
section
1)
Maximum
conductor
cross-
section
Fixing
screw
M12
Fixing
screw
M12
Comment
DIN VDE DIN VDE (Number
of holes)
DIN VDE DIN VDE (Number
of holes)
(Number of
holes)
kW 6SL3710- ... kg mm
2
mm
2
mm
2
mm
2
380 ... 480 V 3 AC
110 1GE32-1AA0 320 2x70 4x240 (2) 2x50 2x150 (2) (2)
132 1GE32-6AA0 320 2x95 4x240 (2) 2x70 2x150 (2) (2)
160 1GE33-1AA0 390 2x120 4x240 (2) 2x95 2x150 (2) (2)
200 1GE33-8AA0 480 2x120 4x240 (2) 2x95 2x150 (2) (2)
250 1GE35-0AA0 480 2x185 4x240 (2) 2x150 2x240 (2) (2)
315 1GE36-1AA0 860 2x240 4x240 (2) 2x185 2x240 (2) (2)
400 1GE37-5AA0 865 3x185 4x240 (2) 3x150 2x240 (2) (10) ground bus
450 1GE38-4AA0 1075 4x150 8x240 (4) 3x185 4x240 (2) (16) ground bus
560 1GE41-0AA0 1360 4x185 8x240 (4) 4x185 6x240 (3) (18) ground bus
500 ... 600 V 3 AC
110 1GF31-8AA0 390 120 4x240 (2) 95 2x150 (2) (2)
132 1GF32-2AA0 390 2x70 4x240 (2) 120 2x150 (2) (2)
160 1GF32-6AA0 390 2x95 4x240 (2) 2x70 2x150 (2) (2)
200 1GF33-3AA0 390 2x120 4x240 (2) 2x95 2x240 (2) (2)
250 1GF34-1AA0 860 2x185 4x240 (2) 2x120 4x240 (2) (2)
315 1GF34-7AA0 860 2x185 4x240 (2) 2x150 4x240 (2) (2)
400 1GF35-8AA0 860 2x240 4x240 (2) 2x185 4x240 (2) (2)
500 1GF37-4AA0 1320 3x185 8x240 (4) 3x150 6x240 (3) (18) ground bus
560 1GF38-1AA0 1360 4x150 8x240 (4) 3x185 6x240 (3) (18) ground bus
660 ... 690 V 3 AC
75 1GH28-5AA0 320 50 4x240 (2) 35 2x70 (2) (2)
90 1GH31-0AA0 320 50 4x240 (2) 50 2x150 (2) (2)
110 1GH31-2AA0 320 70 4x240 (2) 70 2x150 (2) (2)
132 1GH31-5AA0 320 95 4x240 (2) 70 2x150 (2) (2)
160 1GH31-8AA0 390 120 4x240 (2) 95 2x150 (2) (2)
200 1GH32-2AA0 390 2x70 4x240 (2) 120 2x150 (2) (2)
250 1GH32-6AA0 390 2x95 4x240 (2) 2x70 2x185 (2) (2)
315 1GH33-3AA0 390 2x120 4x240 (2) 2x95 2x240 (2) (2)
400 1GH34-1AA0 860 2x185 4x240 (2) 2x120 4x240 (2) (2)
450 1GH34-7AA0 860 2x185 4x240 (2) 2x150 4x240 (2) (2)
560 1GH35-8AA0 860 2x240 4x240 (2) 2x185 4x240 (2) (2)
710 1GH37-4AA0 1320 3x185 8x240 (4) 3x150 6x240 (3) (18) ground bus
800 1GH38-1AA0 1360 4x150 8x240 (4) 3x185 6x240 (3) (18) ground bus
© Siemens AG 2008