Specifications
SINAMICS G150
Drive converter cabinet units
75 kW to 1500 kW
3/31
Siemens D 11 · 2008
3
O p tion s (continued)
M13
Top cable entry,line sid e
T he control cabinet is provided with an additional hood in the
case of a line connection from above. T his hood contains the ter-
minal link s for the power cables as well as the cable clamping
rail for mechanical support of the cables, an E M C shield bus and
a P E rail.
T he cabinet height is increased by 405 mm. T he rails for the con-
nection from above are delivered completely fitted. F or transport
reasons, the hoods are delivered separately and must be fitted
on site. C rane transport assemblies (option M 90) can still be
used. H owever, these must be removed on site in order to fit the
hoods. U se of cable braces should be considered in the case of
small crane hook heights.
A non-drilled mounting plate made of aluminum (5 mm thick )
should be provided on the top of the hood for feeding in the
cables. Depending on the number of cables and the cable
cross-sections used, holes must be provided in this mounting
plate on the plant side for fitting cable glands for introduction of
the cables.
N ote
: T he control cables are still connected from below. W ith
option M 13, the standard line connection from below is not used.
T he hoods have IP 21 degree of protection. In combination with
options M 2 3, M 4 3 and M 54 , additional plastic ventilation grilles
and filter pads are provided.
A ttention
: T he hoods are colored R A L 7 03 5 as standard. If a
special color is req uested for the cabinet (order code Y 09), the
hoods are also painted in this color. V entilation grilles used with
IP 23 , IP 43 and IP 5 4 degrees of protection are colored R A L 7 03 5
and cannot be painted.
T he covers provided with option M 6 0 are included in the scope
of supply.
O ption M 13 cannot be combined with option L 50 (cabinet light
with service sock et) for drive converter cabinet units with power
units connected in parallel.
M21
IP 21 D eg ree o f protectio n
C abinet version in IP 20, but with additional top cover or canopy.
T he cabinet height is then increased by 25 0 mm.
F or transport reasons, the top covers or canopies are delivered
separately and must be fitted on site.
A ttention
: T he top covers or canopies are colored R A L 7 03 5 as
standard. If a special color is req uested for the cabinet (order
code Y 09), the top covers or canopies are also painted this
color.
M23/M43/M54
IP 23/IP 43/IP 54 D eg rees of protectio n
W hen option M 23 , M 43 or M 5 4 is selected, the converter is fitted
with a hood. T he cabinet height is increased by 400 mm. T he
covers used with option M 6 0 are included in the scope of supply.
T hey are a standard part of the cabinet internal air routing and
are adapted accordingly.
F or transport reasons, the hoods are delivered separately and
must be fitted on site.
A ttention
: T he hoods are colored R A L 7 03 5 as standard. If a
special color is req uested for the cabinet (order code Y 09), the
hoods are also painted in this color. T he molded plastic parts
(e.g. ventilation grilles) are colored R A L 7 03 5 and cannot be
painted.
M60
A dd itionalto u ch p rotection
T he drive converter cabinet units are designed as standard in
accordance with B G V A 3 . O ption M 6 0 provides additional cov-
ers (outside normal arm’s reach) in the vicinity of the A C rails and
above the power unit (can only be selected as an option with
converters up to 25 0 k W in the 400 V range, with converters up
to 200 k W in the 5 00 V range and with converters up to 3 15 k W
in the 6 9 0 V range, with degrees of protection IP 20 and IP 21;
otherwise supplied as standard).
M66
Marin e versio n
In accordance with the req uirements of the classification
company:
• Lloyds R egister
• A merican B ureau of Shipping
• G ermanischer Lloyd
• B ureau V eritas
• Det N orsk e V eritas
• C hinese C lassification Society
T his option includes a strengthened mechanical version of the
cabinet, handles (handrail) below the operator panel and me-
chanical lock ing of the cabinet doors. T he cabinet is provided in
the IP 23 degree of protection (option M 2 3) and includes a cabi-
net anti-condensation heating (option L 55). T o attach the con-
verter to the bilge, a welding frame (height 5 mm) is supplied
separately.
N ote
: A combination of options M 2 1, M 2 3 and L 55 is not
possible. If the converter is used for a safety-relevant drive
on the ship, individual certification is necessary (see options
E 11 to E 71).
© Siemens AG 2008