Specifications
SINAMICS G150
Drive converter cabinet units
75 kW to 1500 kW
3/27
Siemens D 11 · 2008
3
Options (continued)
L22/L23
Delivery without line reactor (L22 for converters
"
500 kW )
W ith line reactor 2 % (L23 for converters in single
ciruit > 500 kW )
The line reactor is included in the converter as standard for con-
verters up to 500 kW and for those with power units connected
in parallel. The line reactor (
V
k
= 2 %) is optional for converter
outputs # 500 kW, because converters in this power range are
often connected to the medium-voltage network using trans-
formers adapted to the converter output.
A line reactor is needed for high short-circuit power levels, partly
to protect the actual converter against excessive harmonic cur-
rents, and thus against overload, and partly to limit line harmon-
ics to the permitted values. The harmonic currents are limited by
the complete inductance comprising the line reactor and mains
supply cable inductance. Line reactors can be omitted if the
mains supply cable inductance is increased sufficiently, i. e., the
value of RSC must be sufficiently small.
RSC = Relative Short-Circuit power: Ratio of short-circuit power
S
k line
at the line connection point to fundamental apparent out-
put
S
conv
of the connected converters (in accordance with
EN 50178/VDE 0160).
For SINAMICS G150 drive converter cabinet units:
As, in practice, it is not known on which supply configuration in-
dividual converters are to be operated, i. e., which supply short-
circuit power is present at the converter connection point, it is
recommended that a line reactor is connected on the line side of
the converter.
The line reactor can be omitted (option L22) only if the values for
RSC are lower than those shown in the table. This is the case
when, as shown in the following figure, the converter is con-
nected to the line through a transformer with the appropriate rat-
ing.
As high-output converters are usually connected to medium-
voltage networks using transformers because of the harmonic
effects on the supply, cabinet units in a single circuit with outputs
over 500 kW have no line reactors as standard.
A line reactor (L23 option) is always required, however, if
• for cabinet units > 500 kW, the RSC ratio is > 20, or
• a line filter is used.
L26
Main switch incl. fuses/circuit-breakers
A switch disconnector with fuses is available as the main switch
for converters in a single circuit with ratings up to 800 A. Cabi-
nets with an output current greater than 800 A use a circuit-
breaker instead of a switch disconnector. The circuit-breaker is
controlled and supplied within the converter.
Option L26 is mandatory for converters with parallel-connected
power units and a rated input current of # 1500 A. Circuit-break-
ers are fitted in these units. For parallel-connected converters
with rated input currents of < 1500 A, option L26 can be se-
lected to equip them with fused main switches in addition to the
obligatory line contactors (option L13).
L45
EMERGENCY OFF pushbutton, door mounted
The EMERGENCY OFF button with protective collar is fitted in
the converter cabinet door and its contacts are connected to the
terminal block. The EMERGENCY OFF functions of Category 0
or 1 can be activated in conjunction with options L57, L59 and
L60.
Attention:
By pressing the EMERGENCY OFF button, the motor
is stopped either uncontrolled or controlled depending on the
selected Category 0 or 1, and the main voltage disconnected
from the motor in accordance with IEC 60204-1 (VDE 0113).
Auxiliary voltages (e.g. for separately-driven fans or anti-con-
densation heating) may still be present. Certain areas within the
converter also remain under voltage, e.g. the control function or
auxiliaries. If complete disconnection of all voltages is required,
the EMERGENCY OFF button must be incorporated into a pro-
tection function to be provided on the plantside. An NC contact
is available at terminal –X120 for this purpose.
The EMERGENCY OFF button is preconfigured at the factory
only when one of the options L57 to L60 is selected simulta-
neously. Other circuit arrangements must be implemented on
the plant side.
Type rating Line reactor can be
omitted
Line reactor req uired
kW for RSC Order code
(option)
for RSC Order code
(option)
< 200 " 43 L22 > 43 -
200 ... 500 " 33 L22 > 33 -
# 500 " 20 - > 20 L23
6)((#?-%)( *)%(- )$
?)(/#+-#+
;>%(, *)0 #+ %(*.-
%(".?->(?#
6)(/#+-#+
:%(# +#>?-)+
:%(#
"
& '%(#
9=7233=8<=22245?
V
Connection point of
transformer
Connection point of
converter
Mains power
input inductance
Converter
S
transf
k transf
%
Line
k1
k2 line
G_D011_EN_00022c