Options (continued)
F03, F71, F75, F77, F97
Converter acceptance in the presence of the customer
G 20
CBC10 Communication Board
The CBC10 Communication Board is used to interface the
CU320 Control Unit and thus the SINAMICS G150 to the CAN
(Controller Area Network) protocol. The board’s driver software
fulfills the standards of the following CANopen specification of
the CiA organization (CAN in Automation):
Communication profiles in accordance with DS 301
Drive profile in accordance with DSP 402
(in this case Profile Velocity Mode)
EDS (Electronic Data Sheet)
in accordance with DSP 306
Operating status signaling in accordance with DSP 305
The CBC10 Communication Board plugs into the option slot on
the CU320 Control Unit. The CAN interface on the CBC10 has
2 SUB-D connections for input and output.
G 33
CBE20 Communication Board
The CBE20 Communication Board can be used to connect the
SINAMICS G150 to a PROFINET IO network via a
CU320 Control Unit.
The SINAMICS G150 then assumes the function of a PROFINET
IO device and can perform the following functions:
PROFINET IO device
100 Mbit/s full-duplex
Supports real-time classes of PROFINET IO:
- RT (Real-Time)
- IRT (Isochronous Real-Time), minimum send cycle 500
)s
Connects to controls as a PROFINET IO device using
PROFIdrive compliant with Specification V4
Standard TCP/IP communication for engineering processes
using the STARTER commissioning tool
Integrated 4-port switch with four RJ 45 B sockets based on
the PROFINET AXIC ERTEC400. The optimum topology (line,
star, tree) can therefore be configured without additional exter-
nal switches.
The CBE20 Communication Board plugs into the option slot on
the CU320 Control Unit.
G 61
Additional TM31 customer terminal module
The standard version of the SINAMICS G150 drive converter
cabinet units already contains an Interface Module (TM31 Termi-
nal Module). With a second module, the number of available dig-
ital inputs/outputs and the number of analog inputs/outputs
within the drive system can be expanded.
K 50
SMC30 Sensor Module Cabinet-Mounted
The SMC30 Sensor Module can be used to acquire the actual
motor speed. The signals emitted by the rotary pulse encoder
are converted here and made available via the DRIVE-CLiQ in-
terface of the closed-loop control for evaluation purposes.
The following encoders are supported by the SMC30:
TTL encoders
H TL encoders.
The motor temperature can also be detected using KTY84-130
or PTC thermistors.
Order
code
Description
F03 Visual
inspection
The scope of the acceptance comprises:
• Checking the degree of protection
• Checking the equipment (components)
• Checking the equipment identifier
• Checking the clearance and creepage
distances
• Checking the cables
• Checking the customer documentation
• Submitting the acceptance report
The checks are carried out with the converter
deenergized.
F71 Function test
of the con-
verter without
motor con-
nected
The scope of the acceptance comprises:
• Visual inspection as described for option
F03
• Checking the power supply
• Checking the protection and monitoring
equipment (simulation)
• Checking the fans
• Testing the precharging
• Function test without connected motor
• Submitting the acceptance report
Following the visual inspection in the deener-
gized state, the converter is connected to the
rated voltage. No current flows at the con-
verter output.
F75 Function test
of the con-
verter with
test bay motor
(no load)
The scope of the acceptance comprises:
• Visual inspection as described for option
F03
• Checking the power supply
• Checking the protection and monitoring
equipment (simulation)
• Checking the fans
• Testing the precharging
• Function test with test bay motor (no load)
• Submitting the acceptance report
Following the visual inspection in the deener-
gized state, the converter is connected to the
rated voltage.
A small current flows at the converter’s output
in order to operate the test bay motor (no
load).
F77 Insulation test
on converter
The scope of the acceptance comprises:
• H igh-voltage test
• Measurement of insulation resistance
F97 Customized
acceptance
(on request)
If acceptances are desired which are not cov-
ered by the options F03, F71, F75 or F77,
customized acceptances/supplementary
tests can be ordered using the order code
F97 on request and following technical
clarification.