Specifications

SINAMICS G150
Drive converter cabinet units
75 kW to 1500 kW
3/21
Siemens D 11 · 2008
3
Options (continued)
Mechanical options/electrical options
5)
Option L00 includes option M70.
6)
If the line connection (option M13) and the motor connection (option
M78) are from above, the EMC shield bus (option M70) and the PE
busbar (option M75) are not required in the lower cabinet area.
7)
Can only be selected for converters in the voltage range 400 V up to
250 kW, 500 V up to 200 kW and 69 0 V up to 315 kW. Option M60 is
supplied as standard for larger power ranges.
8)
Option M66 includes option M23.
Rating plate language
Ordering ex amples
Example 1
Tas k :
A drive converter cabinet unit is needed to control the fan speed
for a 380 kW fan drive for connecting to an existing 400 V MCC
outgoing circuit. The rated speed of the fan is 9 75 rpm. As a re-
sult of the ambient conditions, the converter should be mounted
on a 100 mm cabinet base and the degree of protection should
be IP54. The installation altitude is < 1000 m above sea level, the
ambient temperature is 45 °C.
S o lu tio n :
Due to the existing MCC outgoing circuit, the line connection
components, such as main switch, line contactor and line fuses,
can be omitted and the space-saving version C can be selected.
For this constellation, taking into account the derating factors for
IP54 degree of protection and for the increased ambient temper-
ature, a 450 kW, 400 V drive converter cabinet unit must be se-
lected with options
M06 ( 100 mm cabinet base) and
M54 (IP54 degree of protection)
The relevant ordering data are:
6S L3710-1GE38-4CA0-Z
+ M06 + M54
Example 2
Tas k :
A 280 kW pump to control pressure equalization is to be sup-
plied via a converter for a brand new district heating pumping
station. A 69 0 V supply is available. The installation altitude is
350 m above sea level and the ambient temperature 40 °C. The
rated speed of the pump is 740 rpm. The pump unit and motor
are located in an unmanned substation, so the winding temper-
ature of the motor must be monitored by PT100 resistance ther-
mometers and evaluated by the converter. The color of the drive
converter cabinet units is to be RAL 3002.
S o lu tio n :
A 315 kW, 69 0 V version A drive converter cabinet unit must be
selected with the following options:
L26 Main control switch including fuses resp. circuit-breaker
L13 (line contactor),
L86 (PT100 evaluation unit) and
Y09 (special cabinet paint coating).
The relevant ordering data are:
6S L3710-1GH 33-3AA0-Z
+ L26 + L13 + L86 + Y09
Cabinet color R AL 3002
L00 L08 L10 L15 M06 M07 M13 M21 M23 M43 M54 M60 M66 M70 M75 M78 M90
L00 5)
L08
L10
L15
M06
M07
M13 6) 6)
M21 7)
M23 8)
M43
M54
M60 7)
M66 8)
M70 5) 6) 5)
M75 6) 5)
M78 5) 5)
M90
T58 T60 T80
T58
T60
T80
© Siemens AG 2008