Options (continued)
Option selection matrix
Certain options are mutually exclusive. The following tables only
provide an overview. Please refer to the descriptions of the indi-
vidual options for a precise description of options and other ex-
clusions.
E lectrical options
1)
For converters < 500 kW/700 hp, the line reactor (order code L23) is
supplied with the converter as standard.
For converters % 500 kW/700 hp, option L23 must be ordered if
the converters are to be operated on lines with short-circuit power
(RSC > 20) or
a line filter is used (option L00).
2)
Combination L13/L26 is only possible for currents of < 800 A.
Circuit-breakers are used from 800 A upwards. These perform the
same function as options L13 and L26.
3)
Converters in a single circuit require either option L13 or, for currents
of > 800 A option L26 (circuit-breaker).
Converters in a parallel circuit require L13 or L26.
Braking units may also be needed, depending on the drive stopping
time required.
4)
K 82 and L87 can be combined as standard for converters with paral-
lel-connected power units. This combination is available on request
for converters in a single circuit.
possible combination
combination not supported
G20 G33 K50 K51 K82 L00 L13 L15 L19 L22 L23 L26 L45 L50 L55 L57 L59 L60 L61 L62 L83 L84 L86 L87
G20
G33
K50
K51
K82 4)
L00 1)
L13 2) 3) 3) 3)
L15
L19
L22
L23 1)
L26 2) 3) 3) 3)
L45
L50
L55
L57 3) 3)
L59 3) 3)
L60 3) 3)
L61
L62
L83
L84
L86
L87 4)