Specifications
SINAMICS G150
Drive converter cabinet units
75 kW to 1500 kW
3/16
Siemens D 11 · 2008
3
Technical specifications (continued)
Technical specifications for parallel circuit
Note
: The type rating data in hp units are based on the NEC/CEC standards for the North American market.
Note
:
In the case of converters with power units connected in parallel, units with a rated input current of
• <1500 A require option L13.
•
%1500 A require option L26.
(# Selection and ordering data)
1)
Rated output of a typ. 6-pole standard induction motor based on
I
L
or
I
H
at 400 V, 500 V or 690 V 3 AC 50 Hz.
2)
Rated output of a typ. 6-pole standard induction motor based on
I
L
or
I
H
at 460 V or 575 V 3 AC 60 Hz.
3)
The base load current
I
L
is based on a load cycle of 110 % for 60 s or
150 % for 10 s with a load cycle period of 300 s.
See technical specifications (
# Overload capacity).
4)
The base load current
I
H
is based on a load cycle of 150 % for 60 s or
160 % for 10 s with a load cycle period of 300 s.
See technical specifications (
# Overload capacity).
5)
The current values given here are based on the rated output current.
6)
If the main power supply fails and drive control remains active, the
Power Module must be externally supplied with 24 V DC.
The following should also be taken into account:
– CU320: 0.8 A
– TM31: 0.5 A
– AOP30: 0.2 A
– SMC: 0.6 A
– Current requirement of digital inputs/outputs.
7)
The cabinet height is increased by
250 mm for degree of protection IP21,
400 mm for degrees of protection IP23, IP43 and IP54,
405 mm for the M13 and M78 options.
8)
The currents listed here represent the aggregate current of both con-
verter sections.
9)
The power units connected in parallel are supplied as two transport
units.
10)
Longer cable lengths for specific configurations are available on
request.
SINAMICS G150 drive converter cabinet units, version A
Type 6SL3710-
2GE41-
1AA0
2GE41-
4AA0
2GE41-
6AA0
2GF38-
6AA0
2GF41-
1AA0
2GF41-
4AA0
2GH41-
1AA0
2GH41-
4AA0
2GH41-
5AA0
Line voltage 380 ... 480 V 3 AC 500 ... 600 V 3 AC 660 ... 690 V 3 AC
Type rating
• with
I
L
1)
kW 630 710 900 630 710 1000 1000 1350 1500
• with
I
H
1)
kW 500 560 710 560 630 800 900 1200 1350
• with
I
L
at 60 Hz 460 V or 575 V
2)
hp 900 1000 1250 900 1000 1250 – – –
• with
I
H
at 60 Hz 460 V or 575 V
2)
hp 700 900 1000 800 900 1000 – – –
Output current
• Rated current
I
rated
8)
A 1120 1380 1560 860 1070 1360 1070 1360 1500
• Base load current
I
L
3) 8)
A 1092 1340 1516 836 1036 1314 1036 1314 1462
• Base load current
I
H
4) 8)
A 850 1054 1294 770 950 1216 950 1216 1340
Input current
• Rated input
current
5) 8)
A 1174 1444 1624 904 1116 1424 1116 1424 1568
• Input current, max. 1800 2215 2495 1388 1708 2186 1708 2186 2406
• Current requirement auxil-
iary supply 24 V DC
6)
A 2.8 2.8 3.0 2.8 2.8 3.0 2.8 2.8 3.0
Power loss kW 16.2 19.0 19.9 15.4 17.2 23.8 21.3 26.6 29.0
Cooling air requirement
m
3
/s 1.56 1.56 1.56 1.56 1.56 2.96 1.56 2.96 2.96
Cable lengths
between converter and
motor
10)
• Shielded m 300 300 300 300 300 300 300 300 300
• Unshielded m 450 450 450 450 450 450 450 450 450
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB 73/76 73/76 73/76 75/78 75/78 75/78 75/78 75/78 75/78
Dimensions
• Width
9)
mm 2400 2400 2400 2400 2400 3200 2400 3200 3200
• Height
7)
mm 2000 2000 2000 2000 2000 2000 2000 2000 2000
• Depth mm 600 600 600 600 600 600 600 600 600
Weight
(without options), approx.
kg 1700 1710 2130 1700 1700 2620 1700 2620 2700
© Siemens AG 2008