Specifications
SINAMICS G150
Drive converter cabinet units
75 kW to 1500 kW
3/13
Siemens D 11 · 2008
3
Technical specifications (continued)
Technical specifications for single circuit
Note
: The type rating data in hp units are based on the NEC/CEC standards for the North American market.
1)
Rated output of a typ. 6-pole standard induction motor based on
I
L
or
I
H
at 400 V 3 AC 50 Hz.
2)
Rated output of a typ. 6-pole standard induction motor based on
I
L
or
I
H
at 460 V 3 AC 60 Hz.
3)
The base load current
I
L
is based on a load cycle of 110 % for 60 s or
150 % for 10 s with a load cycle period of 300 s.
See technical specifications (
# Overload capacity).
4)
The base load current
I
H
is based on a load cycle of 150 % for 60 s or
160 % for 10 s with a load cycle period of 300 s.
See technical specifications (
# Overload capacity).
5)
The current values given here are based on the rated output current.
6)
If the main power supply fails and drive control remains active, the
Power Module must be externally supplied with 24 V DC.
The following should also be taken into account:
– CU320: 0.8 A
– TM31: 0.5 A
– AOP30: 0.2 A
– SMC: 0.6 A
– Current requirement of digital inputs/outputs.
7)
Version A
: The cabinet height is increased by
250 mm for degree of protection IP21,
400 mm for degrees of protection IP23, IP43 and IP54,
405 mm for the M13 and M78 options.
Version C
: The cabinet height is increased by
250 mm for degree of protection IP21,
400 mm for degrees of protection IP23, IP43 and IP54.
8)
Longer cable lengths for specific configurations are available on
request.
L ine voltage
380 ... 480 V 3 AC
SIN AMICS G 150 drive converter cabinet units
6SL 3710-1G E
32-1... 32-6... 33-1... 33-8... 35-0... 36-1... 37-5... 38-4... 41-0...
Type rating
• with
I
L
at 50 Hz 400 V
1)
kW 110 132 160 200 250 315 400 450 560
• with
I
H
at 50 Hz 400 V
1)
kW 90 110 132 160 200 250 315 400 450
• with
I
L
at 60 Hz 460 V
2)
hp 150 200 250 300 400 500 600 600 800
• with
I
H
at 60 Hz 460 V
2)
hp 125 150 200 250 350 350 450 500 700
O utput current
• Rated current
I
rated
A 210 260 310 380 490 605 745 840 985
• B ase load current
I
L
3)
A 205 250 302 370 477 590 725 820 960
• B ase load current
I
H
4)
A 178 233 277 340 438 460 570 700 860
Input current
• Rated input current
5)
A 229 284 338 395 509 629 775 873 1024
• Input current, max. A 335 410 495 606 781 967 1188 1344 1573
• Current requirement
auxiliary supply
24 V DC
6)
A 1.1 1.1 1.35 1.35 1.35 1.4 1.4 1.4 1.5
P ower loss kW 2.9 3.8 4.4 5.3 6.4 8.2 9.6 10.1 14.4
Cooling air requirement
m
3
/s 0.17 0.23 0.36 0.36 0.36 0.78 0.78 0.78 1.48
Cable lengths
between converter
and motor
8)
• Shielded m 300 300 300 300 300 300 300 300 300
• Unshielded m 450 450 450 450 450 450 450 450 450
Sound pressure
level L
pA
(1 m) at 50/60 Hz
dB 67/68 69/73 69/73 69/73 69/73 70/73 70/73 70/73 72/75
Dimensions
• Width for
version A/C
mm 800/400 800/400 800/400 1000/400 1000/400 1200/600 1200/600 1200/600 1600/1000
• Height
7)
mm 2000 2000 2000 2000 2000 2000 2000 2000 2000
• Depth mm 600 600 600 600 600 600 600 600 600
Weight
(without options) for
version A/C, approx.
kg 320/225 320/225 390/300 480/300 480/300 860/670 865/670 1075/670 1360/980
© Siemens AG 2008