Specifications

SINAMICS G150
Drive converter cabinet units
75 kW to 1500 kW
3/12
Siemens D 11 · 2008
3
Technical specifications (continued)
EMC guidelines
The electromagnetic compatibility describes - in accordance
with the definition of the EMC directive - the "capability of a de-
vice to work satisfactorily in the electromagnetic environment
without itself causing electromagnetic interferences which are
unacceptable for other devices present in this environment". To
guarantee that the appropriate EMC directives are observed, the
devices must demonstrate a sufficiently high noise immunity,
and also the emitted interference must be limited to acceptable
values.
The EMC requirements for "Variable-speed drive systems" are
described in the product standard EN 61800-3. A variable-
speed drive system (or power drive system PDS) consists of the
drive converter and the electric motor including cables. The
driven machine is not part of the drive system. EN 61800-3 de-
fines different limits depending on the location of the drive sys-
tem, referred to as the first and second environments.
The first environment comprises living accomodation or loca-
tions where the drive system is directly connected to a public
low-voltage network without an intermediate transformer.
The second environment is understood to be all locations out-
side living areas. These are basically industrial areas which are
powered from the medium-voltage network via their own trans-
formers.
Four different categories are defined in EN 61800-3 depending
on the location and the power of the drive:
Category C1: Drive systems for rated voltages < 1000 V for un-
limited use in the first environment.
Category C2: Stationary drive systems for rated voltages
< 1000 V for use in the second environment. U se in the first en-
vironment is possible if the drive system is installed and used by
qualified personnel. The warning and installation information
supplied by the manufacturer must be observed.
Category C3: Drive systems for rated voltages < 1000 V for ex-
clusive use in the second environment.
Category C4: Drive systems for rated voltages % 1000 V or for
rated currents % 400 A for use in complex systems in the second
environment.
The following graphic shows the assignment of the four catego-
ries to the first and second environment:
SINAMICS G150 drive converter cabinet units are almost exclu-
sively used in the second environment (categories C3 and C4).
To limit emitted interference, the SINAMICS G150 drive con-
verter cabinet units are equipped as standard with an R FI sup-
pression filter in accordance with the limit values specified in
Category C3. This means that they meet the requirements for in-
dustrial use. Line filters (option L00) are available for use in the
first environment (Category C2).
SINAMICS G150 drive converter cabinet units fulfill the require-
ments for noise immunity defined in EN 61800-3 for the second
environment and consequently also the lower noise immunity
values in the first environment.
The warning and installation information (part of the device
documentation) must be observed.
C1
C2
C3
C4
First
environm ent
Second
environm ent
G_D213_EN_00009