Personal Computer User Manual

Technical data of CPU 31x
7.5 CPU 315-2 PN/DP
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
7-23
Technical data
Routing
Interface X1 configured as
MPI
DP master
DP slave (active)
Interface X2 configured as PROFINET
Yes
Max. 10
Max. 24
Max. 14
Max. 24
CBA (at 50 % communication load)
Maximum data length for arrays and
structures between two partners
Acyclic PROFINET interconnections
Cyclic PROFINET interconnections
Local interconnections
1400 bytes
450 bytes
Slave-dependent
Number of coupled PROFIBUS devices
16
Total of all master/slave connections
1000
Number of device-internal and PROFIBUS
interconnections
500
Number of remote interconnecting partners
32
Remote interconnections with acyclical transmission
Scan rate: Minimum scan interval 500 ms
Number of incoming interconnections 100
Number of outgoing interconnections 100
Remote interconnections with cyclical transmission
Scan rate: Minimum scan interval 10 ms
Number of incoming interconnections 200
Number of outgoing interconnections 200
HMI interconnections via PROFINET (acyclic)
HMI interconnections 500 ms
Number of HMI variables 200
Sum of all interconnections 4000 bytes input/4000 bytes output
Interfaces
1st interface
Type of interface Integrated RS485 interface
Physics RS 485
electrically isolated Yes
Interface power supply
(15 to 30 VDC)
max. 200 mA
Functionality
MPI
Yes
PROFIBUS DP
Yes
Point-to-point communication
No
PROFINET
No