Personal Computer User Manual

Technical data of CPU 31xC
6.5 CPU 314C-2 PtP and CPU 314C-2 DP
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
6-25
Technical data
CPU 314C-2 PtP CPU 314C-2 DP
MPI
Number of connections 12
Services
PG/OP communication
Yes
Routing
No Yes
Global data communication
Yes
S7 basic communication
Yes
S7 communication
As server
As client
Yes
No (but via CP and loadable FBs)
Transmission rates
max. 187.5 kbps
2nd interface CPU 314C-2 PtP CPU 314C-2 DP
Type of interface Integrated RS422/RS485 interface Integrated RS485 interface
Physics RS 422/485 RS 485
electrically isolated Yes Yes
Interface power supply (15 to 30 VDC) No Max. 200 mA
Number of connections None 12
Functionality
MPI
No No
PROFIBUS DP
No Yes
Point-to-point communication
Yes No
DP master
Number of connections 12
Services
PG/OP communication
Yes
Routing
Yes
Global data communication
No
S7 basic communication
No
S7 communication
No
Constant bus cycle time
Yes
SYNC/FREEZE
Yes
Enable/disable DP slaves
Yes
DPV1
Yes
Transmission rates
Up to 12 Mbps
Number of DP slaves per station
Max. 32
Address area
Max. 1 KB I / 1 KB O
User data per DP slave
max. 244 bytes I / 244 bytes O