Personal Computer User Manual

Technical data of CPU 31xC
6.5 CPU 314C-2 PtP and CPU 314C-2 DP
CPU 31xC and CPU 31x, Technical data
6-24 Manual, Edition 08/2004, A5E00105475-05
Technical data
CPU 314C-2 PtP CPU 314C-2 DP
Communication functions CPU 314C-2 PtP CPU 314C-2 DP
PG/OP communication Yes
Global data communication Yes
Number of GD circuits
4
Number of GD packets
Sending stations
Receiving stations
Max. 4
Max. 4
Max. 4
Length of GD packets
Consistent data
max. 22 bytes
22 bytes
S7 basic communication Yes
User data per request
Consistent data
max. 76 bytes
76 bytes (for X_SEND or X_RCV)
64 bytes (for X_PUT or X_GET as the server)
S7 communication
As server
Yes
as client
Yes (via CP and loadable FBs)
User data per request
Consistent data
max. 180 bytes (with PUT/GET)
64 bytes
S5-compatible communication Yes (via CP and loadable FCs)
Number of connections Max. 12
can be used for
PG communication
Reserved (default)
Configurable
Max. 11
1
from 1 to 11
OP communication
Reserved (default)
Configurable
Max. 11
1
from 1 to 11
S7-based communication
Reserved (default)
Configurable
Max. 8
8
from 0 to 8
Routing No Max. 4
Interfaces CPU 314C-2 PtP CPU 314C-2 DP
1st interface
Type of interface Integrated RS485 interface
Physics RS 485
electrically isolated No
Interface power supply (15 to 30 VDC) Max. 200 mA
Functionality
MPI
Yes
PROFIBUS DP
No
Point-to-point communication
No