Now all that remains is to use the PCS7 “User Administrator” utility to make the settings
for each user to have no access to the Area named “IGNORE_ALARMS”.
W
no appear for any user. T
ith this configuration, the alarm for DO_0 will still occur, but the alarm message will
his configuration gives the desired behavior for an Action
Request requiring RBE (so that no TRIGGER changes are missed). This configuration
also gives the proper monitoring and control behavior for the TRIGGER where its alarm
message is not desired. With this configuration the TRIGGER alarm message does not
appear, acknowledgement of the TRIGGER alarm is not necessary, the PCS7 Area button
for “IGNORE_ALARMS” does not appear, and the EventState alarm indications do not
appear. This behavior is made possible by first assigning the DO_0 tag to the
IGNORE_ALARMS folder in DBA and then performing the subsequent configuration in
the PCS7 “OS Proejct Editor” and the PCS7 “User Administrator”.