Setup guide

OSx Migration Cookbook August 30, 2006
8 - PLCs
Old TI PLCs
SIMATIC S5
PLCs
Configuring
SIMATIC S7
PLCs in PCS 7
Configuring
SIMATIC TI505
PLCs in PCS 7
H1 Associations
in the PLC’s
CP1434TF cards
Tistar can communicate with older TI PLCs such as the 520, 530,
and 560 series, and the PM550. PCS 7 cannot communicate with
these. To migrate a Tistar system with these PLCs, their logic
would have to be recreated Simatic S7 series PLCs. The old TI
PLCs would be discarded.
PCS 7 does not support SIMATIC S5 PLCs. Therefore, migrating
an OSx system that uses S5 requires that you recreate their logic on
SIMATIC S7 series PLCs. The S5 PLCs would be discarded.
SIMATIC S7 PLCs are configured through Simatic Manager which
is a standard part of PCS 7. Consult the PCS 7/505 OS Setup Guide
if you plan to include SIMATIC S7 PLCs in your PCS 7/505 OS
project.
SIMATIC TI505 PLCs are configured via DBA. This is done using
the tag files imported into DBA. The first action you need to take
when creating a project through DBA is to configure the PLCs. You
do this by informing DBA which tag files will be used to import
505 tags into you PCS 7 project. This is called “adding an AS
source node” in DBA. DBA then reads the first tag in these files
and configures the PLC to which that tag is assigned. Once DBA
knows about the PLC, you can then enter the PLC’s MAC address
using DBA. When your project is compiled from DBA to WinCC, a
505_PLC tag structure for each TI505 PLC is created.
Each CP1434TF card in a TI505 PLC has a list of the station names
and MAC addresses to which it will be communicating. It does not
have those for your new PCS 7 servers. When migrating to PCS 7,
you will have to add new associations in each CP1434TF module
to which your new PCS 7 system will be connected for each server
that will communicate with that PLC. This is done via the same H1
software you used to do this for your OSx stations.
17