Technical data

Mounting
3-7
SIMATIC Panel PC 670 / 870 Operating Unit, Equipment Manual
Edition 07/02
The clamps and grub screws required for installation are supplied with the
device. Proceed as follows:
1. Insert the complete operating unit and computing unit into the mounting
cut-out prepared as described in Section 3.1, working from the front.
2. From the rear, fix the operating unit in position in the mounting cut-out
using the six clamps (see Figure 3-3) by tightening the grub screws (tor-
que 0.4 - 0.5 Nm).
3. Hook the computing unit into the two hinges (see Figure 3-5).
4. Make the electrical connections.
5. Swing the computing unit to the operating unit and fix in position by tigh-
tening the four knurled screws.
Operating unit
Computing unit
Knurled screw
Knurled screw
Hinge
Hinge
Fig. 3-5 Joining the operating and computing units
Installation with
clamp fixing