Technical data
TS Adapter IE Basic
Manual, 08/2014, A5E02615140-03
55
Error diagnostics
6
6.1
Error Diagnostics Based on LEDs
With the help of the LED displays, simple disruptions can be diagnosed and repaired
independently.
Table 6- 1 LED display for operating state of the TS Adapter IE Basic
LED
Cause
Measures/remedy
RUN
(green/yellow)
ERROR
(red)
MAINT
(yellow)
Illuminated
green
– – The TS Adapter IE Basic is
ready for operation.
–
Off
Off
Off
No power supply
Establish the power supply.
– Lit –
No TS module inserted
Insert a TS module.
TS module defective
Replace the TS module.
Error during the modem
initialization
Open the Web interface of the
TS Adapter IE Basic and have
the errors displayed in the
"Information > Status" tab.
Correct the modem
initialization.
Details about errors can be
found in the LOG file.
–
–
Lit
Unknown or new TS module
Make a firmware upgrade.
Lights up yellow
Lit
–
The firmware is downloaded.
Wait until the
TS Adapter IE Basic is ready
for operation.
Blinks
green/yellow
Flashes Flashes Hardware test and interface
initialization
Flashes yellow 3
times
– – You have restored the factory
settings in the Web interface or
with the reset button RES.
Check to see if the factory
settings fit to your system
configuration.
Flashes – – Firmware update in progress. Wait until the
TS Adapter IE Basic is ready
for operation.
Lights up yellow
Flashes
Off
Error during firmware update
Repeat the firmware update.
Flashes
green/yellow for
3 s
Flashes for 3 s Flashes for 3 s Displays the selected
TS Adapter IE Basic
– any