9.8 Standards, Approvals, Certificates, Guidelines, Labels and Declarations
TS Adapter IE
94 Manual, 06/2008, A5E00977705-02
FM approval
Factory Mutual Approval Standard Class Number 3611,
Class I, Division 2, Group A, B, C, D, T4A.
Class I, Zone 2, Group II C, T4.
WARNING
Injury to persons or damage to property may occur.
In potentially explosive atmospheres there is a risk of injury to persons or damage to
property if you connect or disconnect a live electrical circuit (such as connectors, fuses,
switches) when a TS Adapter IE is in operation.
Do not disconnect live circuits, except where the risk of explosion can be safely excluded.
For use under FM conditions, the TS Adapter IE must be installed in a cubicle with
minimum IP54 protection to IEC 60529.
Safety requirements for mounting
The TS Adapter IE is "open equipment" in accordance with the IEC 61131-2 standard, and
an "open type" in accordance with UL / CSA certification.
The alternative installation methods described below are stipulated in order to ensure safe
operation with respect to mechanical strength, flame resistance, stability and touch
protection:
● Installation in a suitable cabinet
● Installation in a suitable cubicle
● Installation in an appropriately equipped closed switchroom.
Compliance with installation guidelines
The installation guidelines and safety instructions set out in this manual must be observed
during commissioning and operation.
Connecting peripherals
Interference immunity requirements are met when connected to an industrial standard
PC/modem in accordance with EN61000-6-2:2005.