4.2 Setting the PG/PC Interface
Requirements
If you wish to use a remote connection with STEP 7, you need to first set certain
parameters. These settings configure the local interface.
Proceed as follows:
1. Start TeleService and open the "Set PG/PC Interface" dialog box from the
Options menu.
In the "Access Point of the Application" list, select "S7ONLINE (STEP 7)" for
example, if you have installed STEP 7 or "Micro/WIN" if you have installed
STEP 7-Micro/WIN as the access point.
2. In the "Used Interface Configuration" field, select either the "TS Adapter"
interface for the connection to a TS Adapter I/II or the "TS Adapter IE" interface
for the connection to a TS Adapter IE.
3. Click "Properties" to specify additional parameters for the selected interface.
For example, you set a modem or a direct connection for the "TS Adapter"
interface, or a local modem and select your location.
4. For a direct connection, specify the local interface to which your TS Adapter I/II
is connected (for example, COM1 for TS Adapter I or USB for TS Adapter II).
5. Select a local modem and your location.
6. Close the "Properties" dialog box with "OK".
7. Confirm your changes with "OK".
8. You can obtain detailed help about "Set PG/PC Interface" by pressing the F1
key in the dialog box you are working in.
Note
Ensure that the "Access point of your application", for example "S7ONLINE
(STEP 7)", is assigned the correct interface.
If the access point is set to the "TS Adapter" interface, for example, because you
are currently accessing a plant with a TS Adapter I or II, the access point must be
reset to the "TS Adapter IE" interface before accessing a plant with a
TS Adapter IE.