Technical data

Introducing TeleService
TeleService V6.1 Service Software for SIMATIC S7 and C7
1-2 A5E00921336-01
1.2 Functionality of TeleService and Required
Components
TeleService offers the following functionality:
1. Access to remote plants (teleservice):
You can centrally manage, control, and monitor distributed plants by means of
remote connections.
Possible with: S7-200, S7-300, S7-400 and C7 as well as TS Adapter I/II or
TS Adapter IE.
2. Establishing connections from and to remote plants (PG-AS remote link):
You can use PRODAVE MPI V5.0 and higher to establish a remote connection
to a remote plant and the FB 46 "PG_DIAL" function block to establish a
remote connection from a remote plant.
Possible with: S7-400, C7 and TS Adapter I/II.
3. Data exchange between plants (AS-AS remote link):
The FB 47 "AS_DIAL" function block allows two SIMATIC automation systems
to exchange process data via the phone network.
Possible with: S7-200 (restricted), S7-400, C7 and TS Adapter I/II.
4. Sending an SMS from a plant:
Using the function block FB 48 "SMS_SEND", a SIMATIC automation system
can send a message (SMS) via a GSM radio modem.
Possible with: S7-300, S7-400, C7 and TS Adapter I/II.
5. Sending e-mail from a plant
Using the function block FB 49 "AS_MAIL", a SIMATIC automation system can
send e-mail.
Possible with: S7-300, S7-400 and TS Adapter IE.
TS Adapter Library
The independent TeleService S7 Library setup make available the function blocks
FB 46 "PG_DIAL", FB 47 "AS_DIAL", FB 48 "SMS_SEND" and FB 49 "AS_MAIL"
as well as examples for S7-300, S7-400 and C7.
The TeleService S7 Library integrates itself in an existing STEP 7 installation. The
installation requires STEP 7 V5.0 or higher.
You can only use the function blocks in combination with the employed
TS Adapter:
for TS Adapter I/II:
FB 46 "PG_DIAL", FB 47 "AS_DIAL" and FB 48 "SMS_SEND"
for TS Adapter IE:
FB 49 "AS_MAIL"