Technical data
Appendix
A.3 General technical specifications
TS Adapter II
56 Manual, 06/2008, A5E00272728-03
Sinusoidal Interference
The table below shows the electromagnetic compatibility of the TS Adapter II in relation to
sinusoidal interference.
Table A-2 Sinusoidal Interference
Sinusoidal interference Test values Degree of
severity
HF irradiation (electromagnetic fields) according to
IEC 61000-4-3
10 V/m with 80% amplitude modulation of 1 kHz
in the range from 80 MHz to 1000 MHz and 1.4
GHz to 2 GHz
1 V/m with 80% amplitude modulation of 1 kHz
over the range from 2 GHz to 2.7 GHz
3
RF interference current on supply, cables and
cable shielding conforming to IEC 61000-4-6
Test voltage 10 V, with 80% amplitude modulation
of 1 kHz in the 10 MHz to 80 MHz range
3
Emission of Radio Interferences
Interference emission of electromagnetic fields according to EN 55011: Limit value class A,
Group 1.
Additional measures
If you want to operate the TS Adapter II in an office environment, you must ensure
compliance with limit class B to EN 55022.
Take suitable measures for increasing resistance to high external interference levels as
required.